FieldServer FS-8704-16 Manuel D’Utilisation

Page de 40
FS-8704-16 Omron FINS Manual 
 
 
 
 
Page 1 of 37 
 
 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA  Web:www.fieldserver.com 
Tel: (408) 262-2299   Fax: (408) 262-9042   Toll_Free: 888-509-1970   email: support@fieldserver.com 
1. 
 Omron FINS Description  
The Ethernet Omron FINS driver allows the FieldServer to transfer data to and from 
devices over Ethernet using Omron FINS protocol. The FieldServer can emulate either 
a Server or Client.  
FINS is an Omron protocol which can be used by a PLC program to transfer data and 
perform other services with a remote PLC connected on an Ethernet Network.  It can 
also be used by remote devices such as PC’s and FieldServer’s to transfer data and 
perform other services. 
The protocol uses the Ethernet protocol called UDP to carry the FINS messages back 
and forth. The UDP protocol is not connection based and reliability is achieved by using 
confirmation messages. 
This Ethernet Driver can be used to transfer data to and from the Nodes supporting 
FINS communications. 
Max Nodes Supported 
FieldServer Mode  Nodes 
Comments 
Client 126 
Omron limit the set of permitted nodes to 126. They are 
numbered 1 to 126 corresponding to the last byte of the 
remote node IP address.
 
Server 20 
The FieldServer can emulate a maximum of 20 Omron 
FINS servers.