FieldServer IR-148 Manuel D’Utilisation

Page de 19
FS-8700-102 Honeywell Zellweger IR-148-8_8-Channel Manual  
 
Page 3 of 19 
 
 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA  Web:www.fieldServer.com 
Tel: (408) 262-2299   Fax: (408) 262-9042   Toll_Free: 888-509-1970   email: support@fieldServer.com 
1. 
Honeywell Zellweger IR-148 Description 
The  Honeywell  Infrared  Gas  Monitor  (Model  IR-148)  detects  solvents  and  gases  such  as 
HCFCs,  HFCs  and  PFCs.  IR-148  can  have  1,  4  or  8  sampling  points.    This  InfraTox  driver 
reports gas values, alarms and troubles from IR-148 having either 1 or 8 sampling points. 
The  serial  driver  can  emulate  a  client  or  a  server.    The  FieldServer  and  IR-148  device  are 
connected using a RS-485 network. 
 
As a Client:  The driver listens passively for messages from the Honeywell Zellweger IR-148     t 
and  stores  data  extracted  from  the  messages.    The  driver  cannot  poll  the  IR-148  device  for 
data.    The  driver  records  some  additional  data  age  information  (which  is  stored  in  the 
FieldServer’s  Data  Arrays)  because  messages  do  not  always  contain  information  about  all 
sensors  and  depending  on  the  IR-148  operational  mode  (e.g.  Locked  mode.),  may  never 
contain information other than for one sensor. 
 
As a Server:  The Server side of this driver has been developed primarily to test the Client side 
driver as part of FieldServer’s QA program.  The driver sends messages reporting the state of 
the samples.  The Server driver can also be locked to report the status/value of one particular 
sample channel. 
 
It  is  possible  to  connect  two  Honeywell  Zellweger  units  (IR-148)  on  one  RS-485  network 
provided that one unit is configured as a single point unit (IR-148 1 point) and the other as an 8 
point unit (IR-148 8 point).  At this stage only one device with 8 points has been tested. 
 
To allow for the possibility that the device is connected on a RS-485 network with other devices 
(such as the relay module option) messages that are not 49 bytes long and which do not begin 
with 0xB1 will be ignored.  The Driver will, however, provide statistics for the ignored as well as 
the processed messages. 
 
To see supported messages and the way the Driver stores Data, refer to Appendix A.2 
 
Max Nodes Supported 
FieldServer Mode 
Nodes 
Comments 
Client 
Tested only 1 node (IR-148 8 Point) per port
 
Server 
Developed to test Client side of the Driver.