Roberts Gorden CTHN-80 Manuel D’Utilisation

Page de 48
SECTION 8: U
NITARY
 L
INEAR
 & U-T
UBE
 H
EATER
 I
NSTALLATION
  
21
Step 8.7.2 Coupling and Tube Assembly (Continued)
Step 8.8 Turbulator Installation
2.3 m       .25 m
3 m       .25 m
Model
Radiant
Tube Length
CTHN-40
10' (4.5 m)
CTHN-60
20' (6 m)
CTHN-80
20' (6 m)
CTHN-100
30' (9 m)
CTHN-125
40' (12 m)
CTHN-150
40' (12 m)
CTHN-175
50' (18 m)
CTHN-200
50' (18 m)
Tw
ist
Pull String
Tab
Fold tab around outside
of tube nearest to the vent to
hold turbulator in place.
Turbulator
Section
Turbulator
Adapter
Description
Part Number
Turbulator Adapter
03051503
Turbulator Section
03051504
Turbulator Section (Stainless)
03051505
Tube
91409XXX
Turbulator must be installed in the last
standard section of radiant tube. 
Turbulator is only required on the 
CTHN-40, CTHN-60 and CTHN-80.
Turbulator Installation
Model
Tube Section
CTHN-40
1st 10' (3 m) Section
CTHN-60
2nd 10' (3 m) Section
CTHN-80
2nd 10' (3 m) Section
CTHN-100
N/A
CTHN-125
N/A
CTHN-150
N/A
CTHN-175
N/A
CTHN-200
N/A
Turbulator section
(stainless) used in 
CTHN-40 heaters must be in the 
section of tube nearest to the burner.