SECTION 1: H
EATER
 S
AFETY
1
SECTION 1: HEATER SAFETY
Your Safety is Important to Us!
This symbol is used throughout the manual 
to notify you of possible fire, electrical or burn 
hazards. Please pay special attention when 
reading and following the warnings in these 
sections.
This heater is designed for heating non-residential indoor 
spaces. Do not install in residential spaces. These 
instructions,
 layouts , AS5601/AG 601,local codes and 
ordinances, and applicable standards that apply to gas 
piping, electrical wiring, venting, etc., must be thoroughly 
understood before proceeding with the installation.
SECTION 2: INSTALLER RESPONSIBILITY
• To install the heater, as well as the gas and electrical 
supplies, in accordance with applicable specifications 
and codes. Roberts-Gordon recommends the 
installer contact a local building inspector or Fire 
Marshal for guidance.
• To use the information given in a layout drawing and 
in the manual together with the cited codes and 
regulations to perform the installation.
• To install the heater in accordance with the Clear-
ances to Combustibles.
• To furnish all needed materials not furnished as 
standard equipment.
• To plan location of supports.
• To provide access to burners for servicing on all 
sides, for burner removal.
• To provide the owner with a copy of this installation, 
operation and service manual.
• To never use heater as support for ladder or other 
access equipment and never hang or suspend any-
thing from heater.
2.1 
Low Level User Instructions
In all situations, clearances to combustibles must be 
maintained. Failure to observe clearances to 
combustibles can result in death, severe injury or 
property damage. Signs should be posted in storage 
areas to specify the maximum stacking height of items 
placed below heater to maintain required clearances to 
combustibles. Minimum clearances must be maintained 
from vehicles parked below the heater. Caution should be 
used when running the system near combustible 
materials such as wood, paper, rubber, etc. 
Consideration should be given to partitions, storage 
racks, hoists, building construction,etc.
A wall tag is supplied with the BLACKHEAT® heater as a 
permanent reminder of the safety instructions and the 
importance of the minimum required clearances to  
combustibles. A copy of the wall tag is illustrated on Page 
2, Figure 1
. Peel off the backing of the adhesive strips on 
the rear surface of the tag and position the tag on a wall 
near the BLACKHEAT® heater (e.g. thermostat or 
ROBERTS GORDON
®
 BZC Microprocessor Controller).
2.2 
Halogenated Hydrocarbons
Roberts-Gordon cannot be responsible for ensuring that 
all appropriate safety measures are undertaken prior to 
installation; this is entirely the responsibility of the 
installer. It is essential that the contractor, the sub-
contractor, or the owner identifies the presence of 
combustible materials or halogenated hydrocarbons* 
anywhere in the premises.
* Halogenated Hydrocarbons are a family of chemical com-
pounds characterized by the presence of halogen elements 
(flourine, chlorine, bromine, etc.). These compounds are 
frequently used in refrigerants, cleaning agents, solvents, etc. If 
these compounds enter the air supply of the burner, the lifespan 
of the heater components will be greatly reduced. An outside air 
supply must be provided to the burners whenever the presence 
of these compounds is suspected. Warranty will be invalid if the 
heater is exposed to halogenated hydrocarbons.
2.3 
National Standards and Applicable Codes
All Appliances must be installed in accordance with the 
latest revision of 
AS5601/AG 601 and other relevant  
codes. This refers also to the electric, gas and venting 
installation. Note: Additional standards for installations in 
Public Garages, Aircraft Hangars, etc. may be applicable.
WARNING
Installation, Service and Annual Inspection of heater
must be done by a contractor qualified in the
installation and service of gas-fired heating equipment.
Read this manual carefully before installation,
operation, or service of this equipment.
Failure to follow these instructions can result in death,
injury or property damage.
CAUTION
Do not use heater in an area containing corrosive
chemicals.
Avoid the use of corrosive chemicals to ensure a
longer life of the burner, tubing and other parts.
Failure to follow these instructions can result in