Heat & Glo LifeStyle TIARAP-BK Manuel D’Utilisation

Page de 56
August 1, 2008
Page  11
Heat & Glo · Tiara Petite B · 7026-101K
 
 
 
 
 
 
25' 
24' 
 
22' 
 
20' 
 
18' 
 
16' 
 
14' 
 
12' 
 
10' 
 
8' 
 
6' 
 
4' 
 
2' 
6 in. (152mm) Minimum starter pipe 
30 in. (762mm) Maximum Horizontal run with no vertical pipe and with 1/4 in. 
(6mm) rise per foot. Must use approved Termination Cap.
25 ft. (8m)  
Maximum Vertical 
    2'        4'         6'        8'        10'      12'     14'  15' 
Termination cap
Termination cap
Example 1 
Example 2 
Adjust 
Intake 
Damper 
SLK-01TRD or an approved Termination Cap
 
 
 
6 ft. (2m) Minimum  
Vertical Termination 
 
VERTICAL DISTANCE 
FROM APPLIANCE TO 
90° ELBOW 
Install Flue 
Restrictor
Adjust 
Intake 
Damper 
D. 
How to Use the Vent Graph
E. 
Venting Guidelines
1
.  Measure the distance from the top of appliance to the 
center of the 90° elbow. On the graph below, draw a 
horizontal line from that measurement on the vertical 
axis across until it intersects with the slanted line.
2.  From the point of this intersection, draw a vertical line to 
the bottom of the graph.
3.  The point at which this line meets the bottom line of the 
graph is the maximum length of the horizontal run. 
Example 1:  If the vertical dimension from the top of the 
appliance to the center of the 90° elbow is 7 ft. (2m), the 
horizontal run to the outer wall fl ange must not exceed 9 
ft.-8 in. (3m).
.
Example 2: If the vertical dimension from the top of the 
appliance is 21 ft. (6m), the horizontal run to the outer wall 
fl ange must not exceed 4 ft.-3 in. (1m).
4.  Each 90° elbow is equivalent to 3 ft. (914mm) of vent 
pipe and each 45° elbow is equivalent to 1 ft. (305mm) 
of vent pipe, and must be subtracted from vent pipe 
run. A single vertical to horizontal 90° elbow is already 
calculated into the allowable 15 ft. (5m) run. Each 
additional 90° elbow reduces the maximum horizontal 
distance by 3 ft. (914mm).
Example:  The use of three elbows would reduce the 
allowable horizontal run to 9 ft. (3 - 1 = 2 elbows 
x 3 ft. = 6 ft.; 15 ft. max. - 6 ft. = 9 ft. max.)
Notes:   
•  The maximum horizontal vent run is 15 ft. (5m) when the 
vertical vent rise is 10 ft. (3m).
•  Horizontal sections require a 1/4 in. (6mm) rise for every 
12 in. (305mm) of horizontal travel.
•  Exterior vent diameter = 6-5/8 in. (168mm); Inner vent 
diameter = 4 in. (102mm).
•  Horizontal sections require noncombustible support every 
3 ft. (914mm) , e.g. wall straps.
•  For any vertical termination a minimum of 6 ft. (2m) 
vertical must be used.
EXCEPTIONS FOR HORIZONTAL INSTALLATIONS:
*The maximum horizontal vent run is 30 in. (762mm).
*The maximum horizontal vent run with a 45° elbow is 
18 in. (457mm).
*No external minimum rise is required.  
*The minimum horizontal vent run is 6 in. (152mm).
Figure 5.2
NOTE:  In the Commonwealth of Mas-
sachusetts the word damper shall be 
replaced with the words fl ue restrictor.