IM-106-4050 Original Issue
March 2006
OxyBalance Oxygen Display
and Averaging System
http://www.processanalytic.com
Section 3
Setup
OVERVIEW
This section provides information on setup and configuration of the 
OxyBalance Oxygen Display and Averaging System
SETUP
Each O
probe generates a 4-20 mA output signal that is received by the 
OxyBalance system. When a probe channel detects a current signal greater 
than 3.5 mA, that probe is considered active, and is automatically made 
available. It is not necessary to tell the OxyBalance that a probe is present. It 
is automatically detected and used. Table 3-1 shows how the OxyBalance 
system interprets and displays these signals.
Table 3-1.  Signal Interpretation
After these signals are converted into an O
2
 % they are displayed on the 
touch screen interface. The rest of this section will outline the necessary steps 
to configure and operate the OxyBalance system through the touch screen 
interface. 
Before starting to install this equipment, read the "Safety Instructions" in Appendix A: Safety 
Data. F
ailure to follow the safety instructions could result in serious injury or death.
Disconnect all power before installing or replacing components. Failure to disconnect power 
may result in electrical shock and/or damage to the equipment.
4-20 mA Signal Value
Status
Display Color
<3.5 mA
Probe Inactive
Not Shown
3.5 mA to 3.6 mA
Probe Failed
Red
3.6 mA to 3.8 mA
Reading Under Range
Yellow
3.8 mA to 20.5 mA
Good Reading
Green
20.5 mA to 21 mA
Reading Over Range
Yellow
>21 mA
Probe Failed
Red