GLOBAL SETUPS
Alarm Inputs
Program alarm inputs for normally opened operation, normally closed operation, or disabled.
Normally Closed
= current flow
= alarm switch or relay closed
Normally Open
= no current flow
= alarm switch or relay open
Figure 19.  Alarm Wiring Example
ALARMS
COM-IN
COM-OUT
12 VDC
  1   2   3   4   H   0
OUT
IN
SVHS
VCR
MAIN
SVHS
75 OHMS
  1 2 3 4
SPOT
IN
OUT
1
2
3
4
VCR (STANDARD OR SVHS)
VIDEO INPUT
CORRESPONDS
TO ALARM INPUT
GROUND
ALARM
RECORD
SIGNAL
In the example in Figure 19, current flows through the contacts (switch) in the door when
it is closed. When the door is open, no current flows. To cause an alarm when the door
is opened, program the alarm input for normally closed (door is normally closed). To
cause an alarm when the door is closed, program the alarm input for normally open.
To globally set alarm inputs, select OPENED, CLOSED, or DISABLED.
To individually set alarm inputs, refer to the 
Camera Setup
 section.
To determine how alarms are recorded and for how long, refer to the 
Record
Setup
 section.
Dwell Rates
Sets the sequence dwell rate (how long each camera’s view is sent to the multiplexer)
in seconds for all cameras. To set individual rates, refer to the 
Sequence Setup
 section.