Avaya S8100 Manuel D’Utilisation

Page de 408
1 Install and cable a G600 cabinet
Check AC power and ground for G600
74
S8100 Installation and Upgrades
November 2003
Floor grounds are those grounds on each floor of a high-rise building that are suitable for connection to 
the ground terminal in the riser closet and to the cabinet’s single-point ground terminal. Approved floor 
grounds may include:
Building steel
The grounding conductor for the secondary side of the power transformer feeding the floor
Metallic water pipes
Power-feed metallic conduit supplying panel boards on the floor
A grounding point specifically provided in the building for the purpose
Uninterruptible power supply
A recommended uninterruptible power supply (UPS) may be used for power holdover. The type of UPS 
depends on the holdover requirements. Total holdover capacity varies depending on the UPS. The UPS 
must provide surge protection for the G600 cabinet.
CAUTION:
The major-alarm contacts should only be connected to a UPS that can indicate its backup 
power status. For most non-Avaya UPSs, you should not use the major external device 
leads. Using these leads for anything else could cause an SPE download.
1
Connect the UPS to an electrical outlet capable of handling the power requirements of the 
cabinets:
a
100 VAC, 4.5 Amps
b
120 VAC, 3.8 Amps
c
200 VAC, 2.3 Amps
d
220 to 240 VAC, 2.0 Amps
2
Ensure that the cabinet is connected to an “unswitched” or “always-on” electrical outlet on the 
UPS.
3
For an Avaya UPS, connect and administer the UPS. See 
NOTE:
If an Avaya UPS is wired as recommended, holdover time for each power outage is 1 
minute before an automatic shutdown. UPS may handle any subsequent power outage 
based on its total battery capacity.
Cabinet’s power switch
!
DANGER
:
The latch acts as the DC power switch and only removes DC power from the cabinet, 
not
 AC power. To remove AC power, pull the AC power cord from the appliance 
inlet. See