Specifications
NOTE: Specifications are subject to change without prior notice.
Physical Specifications
Dimensions: L×W×H
254×355.6×63.5 mm (10×14×2.5 in.)
Weight 1 kg
(2.2 lbs)
Xanbus ports
2
AC Main
1 set of split-phase pass-through terminals
(L1, N, L2, G) accessible by removing the
AC Main panel cover
(L1, N, L2, G) accessible by removing the
AC Main panel cover
AC relay terminal
blocks
blocks
6 pairs I/O terminal blocks - one pair for
each AC relay (PN: 809-0912)
4 pairs I/O terminal blocks - one pair for
each AC relay (PN: 809-0913)
each AC relay (PN: 809-0912)
4 pairs I/O terminal blocks - one pair for
each AC relay (PN: 809-0913)
DC auxiliary
connector port
connector port
4 (3-pin connector for each DC relay)
1 (2-pin connector for one B+ signal)
1 (2-pin connector for battery)
1 (2-pin connector for one B+ signal)
1 (2-pin connector for battery)
Environmental Specifications
Operating range
–20 to 50 °C (– 4 to 122 °F)
Electrical Specifications
AC Main input voltage
120/240 VAC single/split phase
AC Main input current Split phase: 50 AAC per phase
Dual in phase: 30 AAC per phase
DC input voltage from
battery source
battery source
12/24 VDC
AC relay input voltage
120 VAC
AC relay input current
15 AAC per circuit
DC relays input voltage 12/24 VDC
DC relays input
current
current
5 ADC per circuit
Regulatory Approvals
Safety
UL 916,
CSA C22.2 No. 205
CSA C22.2 No. 205
EMC
FCC Part 15, Class B
FSequence IPM Owners Guide.book Page 41 Thursday, October 6, 2011 3:33 PM