Access Power Rectifiers 
Two types of fan-cooled, hot-pluggable Access Power Rectifiers are available. 
• 
APU48 – 48 V, 720 W, (120 - 240 V AC) 
• 
APR48 – 48 V, 1500 W, (208 - 240 V AC) 
There are three status indicator LEDs on the Access Power Rectifier front panel (Power On, 
Urgent Alarm and Non-Urgent Alarm). 
Details about replacing a rectifier can be found in Chapter 7. 
 
 
 
"
  Power On LED (Green) – indicates that the rectifier is 
powered. 
#
  Non-Urgent Alarm LED (Yellow) – indicates non-critical 
conditions, such as: 
• 
Rectifier in power/current limit mode 
(This normally happens for a short period of time 
when the batteries are recharging.)
 
• 
Rectifier operating in temperature turndown mode, 
because of high ambient temperature or low AC 
supply voltage 
$
  Urgent Alarm LED (Red) – indicates critical fault 
conditions, that require urgent attention, such as: 
• 
Rectifier failed
 
• 
Rectifier shut down
 
• 
AC supply failed (green LED off)
 
• 
Very high AC supply voltage
 
• 
DC overvoltage
 
Retaining Screw (loosen to remove rectifier)
 