Eaton Electrical SC200 Manuel D’Utilisation

Page de 78
Communications 
6-4 
Copyright © 2005-2006 Eaton Corporation.  All Rights Reserved. 
IPN 997-00012-41D    December 2006 
 
 
Setting Up SNMP Traps 
The SM45 supervisory module can be configured to send alarms as SNMP traps to up to 
eight different SNMP trap receivers. 
To send alarms as SNMP traps, first set up Ethernet communications (see page 6-3 for 
details), and then use DCTools to set up SNMP traps as follows: 
 
From the DCTools System Summary (Home) screen, click the Configuration and then 
Communications hotlink to display the Communications view. 
Click the   button to the left of SNMP to display the SNMP configuration view. 
Do not change the default settings of SNMP Read Community (public) and SNMP 
Write Community
 (private), unless requested by the network administrator. 
Configure Trap Repeat and Trap Repeat Rate as appropriate. 
For each receiver, configure the following parameters using the configuration guidelines. 
 
Parameter Configuration 
Guidelines 
Name 
Enter the name of the SNMP trap receiver (20 characters 
maximum). 
Level 
SNMP Trap Level – controls reporting of specific events for each 
receiver as follows: 
• 
Select All Events And Alarms to receive events and urgent 
and non-urgent alarms.  (Typically events are status 
messages such as Equalize Active.) 
• 
Select Urgent And Non Urgent Alarms to receive both 
urgent and non-urgent alarm notifications. 
• 
Select Urgent Alarms Only to receive only urgent alarm 
notifications. 
• 
Select Disabled to temporarily disable notifications to the 
receiver. 
IP Address 
Enter the IP address of the trap receiver that has been assigned 
by the network administrator. 
Port 
Enter the port number of the trap receiver that has been 
assigned by the network administrator. 
Trap Community 
A form of password.  Use public, unless the network 
administrator has assigned a new password. 
Mode Select: 
• 
Normal Traps for sending traps to any network 
management system, except PowerManagerII 
• 
Acknowledged Summary Trap for sending traps to 
PowerManagerII only