Glossary of Alarms
 
 
 
Copyright © 2005-2006 Eaton Corporation.  All Rights Reserved. 
IPN 997-00012-41D    December 2006 
A-1
 
 
AC Fail 
All rectifiers are reporting loss of AC power. 
 
ACD Fan Fail 
The AC Distribution cooling system or fan controller has failed. 
 
Aux Temp High 
The auxiliary temperature sensor is at a temperature above the high 
temperature set point. 
 
Aux Temp Low 
The auxiliary temperature sensor is at a temperature below the low 
temperature set point. 
 
Aux Temp Sensor Fail 
The auxiliary temperature sensor is incorrectly configured, 
disconnected, not fitted or faulty. 
Batt Temp High 
This alarm indicates either thermal runaway of the batteries or that 
the batteries are operating at a temperature that may cause reduced 
battery life. 
 
Batt Temp Low 
This alarm indicates a risk to the battery standby power system.  
Note that lower temperatures reduce the battery capacity. 
 
Battery Fuse Fail 
(displayed as Batt Fuse Fail)
 
The batteries may no longer be powering the load. 
 
 
 
Battery Test Active 
A Battery Test is active. 
 
Battery Test Fail 
The batteries do not have the required capacity or are not operating 
in a fully charged state. 
 
Equalize Active 
An Equalize process is active. 
 
Fast Charge Active 
A Fast Charge process is active. 
 
High Float 
The float voltage is above its normal range. 
 
High Load 
The bus voltage is higher than the range that is safe for a reliable 
load. 
 
In Discharge 
The batteries are discharging. 
 
Load Fuse Fail 
The Load Fuse Fail digital input to the SM45 is active. 
 
Low Float 
The float voltage is below its normal range. 
 
Low Load 
The bus voltage is below its normal range.