Emerson 5400 Manuel D’Utilisation

Page de 42
Manual Supplement
00809-0500-4530, Rev AA
October 2010
Rosemount 5300/5400 Series
1-28
Table 1-16.  Output Variables for 
Floating Point Format Code 3
Slave 1 SV
2104
Secondary variable from slave 1 
represented in IEEE 754 format, using 
Floating Point Format Code 2.
Slave 1 TV
2106
Tertiary variable from slave 1 
represented in IEEE 754 format, using 
Floating Point Format Code 2.
Slave 1 FV (QV)
2108
Fourth variable from slave 1 represented 
in IEEE 754 format, using Floating Point 
Format Code 2.
Register Name
Register Number
Note
Register Name
Register Number
Note
Slave 1 Status
2200
Bit information in bitfield:
Bit 0: Invalid Measurement Slave 1 PV.
Bit 1: Invalid Measurement Slave 1 SV.
Bit 2: Invalid Measurement Slave 1 TV. 
Bit 3: Invalid Measurement Slave 1 FV.
Bit 14: HART bus busy (slave in burst or 
other master present)
Bit 15: HTM Task not running (option not 
available).
Note: Bit 1-3 is set when Invalid 
Measurement of Slave 1 Non PV, i.e. all 
three bits are set simultaneously.
Slave 1 PV 
2202
Primary variable from slave 1 
represented in IEEE 754 format, using 
Floating Point Format Code 3.
Slave 1 SV
2204
Secondary variable from slave 1 
represented in IEEE 754 format, using 
Floating Point Format Code 3.
Slave 1 TV
2206
Tertiary variable from slave 1 
represented in IEEE 754 format, using 
Floating Point Format Code 3.
Slave 1 FV (QV)
2208
Fourth variable from slave 1 represented 
in IEEE 754 format, using Floating Point 
Format Code 3.