Manual Supplement
00809-0500-4530, Rev AA
October 2010
Rosemount 5300/5400 Series
1-32
Thermo Electron Autopilot
Figure 1-12. Wiring Diagram for 
Connecting 5300/5400 Modbus to 
Thermo Electron Autopilot
Table 1-22.  Parameter Values (in 
case of Thermo Electron Autopilot)
The Input Register Base Number needs to be added to the Input Register 
address of the 5300/5400 transmitter. In this case, register 1302 needs to 
have 1302 entered as the address etc.
Bristol ControlWave Micro
Figure 1-13. Wiring Diagram for 
Connecting 5300/5400 Modbus to 
Bristol ControlWave Micro
Table 1-23.  Parameter Values (in 
case of Bristol ControlWave Micro)
The Input Register Base Number needs to be added to the Input Register 
address of the 5300/5400 transmitter. In this case, register 1302 needs to 
have 1303 entered as the address etc.
CEB TB1
1 RX +
2 RX -
MA
MB
POWER +
POWER -
AutoPILOT
5300/5400 Modbus
Power Supply
+ 8 to + 30 Vdc 
(max. rating)
GND
Parameter
Value
Baud Rate
9600
Floating Point Format Code
1
RTU Data Type
IEEE Flt 2R
Input Register Base Number
0
Com Port 3 (C3) RS-485
1
2
3
4
5
TXD-
TXD+
GND
6
7
8
9
MA
MB
POWER +
POWER -
ControlWave Micro
5300/5400 Modbus
Power Supply
+ 8 to + 30 Vdc 
(max. rating)
GND
DB9 Male
Parameter
Value
Baud Rate
9600
Floating Point Format Code
2 (FC 4)
RTU Data Type
32-bit registers as 2 16-bit registers
Input Register Base Number
1