Chapter 9 Installation and Wiring
 
9-5 
 
 
(4) Mount the wire duct as it is needed. 
                If the clearances are less than those in Fig below, follow the instructions shown below 
 
               
 
If the wire duct is mounted on the upper part of the PLC, make the wiring duct    clearance 50 ㎜  or less for good   
ventilation. Also, allow the distance enough to press the hook in the upper part from the upper part of the PLC. 
             
 
If the wire duct is mounted on the lower part of the PLC, make optic or coaxial cables contact it and consider the   
minimum diameter of the cable. 
 
(5) To protect the PLC from radiating noise or heat, allow 100 ㎜  or more clearances between it and parts. Left or right 
clearance and clearance from other device in the left or right side should be 100 ㎜ or more. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
(6) MASTER-K120S has hooks for DIN rail in the base unit and expansion modules. 
 
 
 
 
 
 
 
 
 
 
 
 
 
                                                                         
 
High voltage   
device 
 
Other 
device 
100mm or more
Heat generating device 
80mm
 
or more 
80mm
 
or more 
DIN rail 
K7M-DR30U