Lg Electronics 120S Manuale Utente

Pagina di 306
Chapter 7    Usage of Various Functions
 
7-3 
 
 
 
4) External interface circuit 
 
Signal name 
I/O 
Internal circuit 
Termi
nal 
No. 
1Phase 
2Phase 
Operati
on 
Input warranted 
voltage 
On 20.4~28.8V 
P00 
Ch0  
Input 
pulse 
Ch0 A 
Phase 
Input  
Off 
6V or lower 
On 20.4~28.8V 
P01 
Ch1  
Input 
pulse 
Ch0 B 
Phase 
Input 
Off 
6V or lower 
On 20.4~28.8V 
P02 
Ch2  
Input 
pulse 
Ch2 A 
Phase 
Input  
Off 
6V or lower 
On 20.4~28.8V 
P03 
Ch3  
Input 
pulse 
Ch2 B 
Phase 
Input 
Off 
6V or lower 
Input 
 
COM
Common  
On 20.4~28.8V 
P04 
Ch0 
Preset 
input 
Ch0 
Preset 
input 
Off 
6V or lower 
On 20.4~28.8V 
P05 
Ch1 
Preset 
input 
Off 
6V or lower 
On 20.4~28.8V 
P06 
Ch2 
Preset 
input 
Ch2 
Preset 
input 
Off 
6V or lower 
On 20.4~28.8V 
P07 
Ch3 
Preset 
input 
Off 
6V or lower 
Input 
 
COM
Common  
 
5) Wiring instructions 
A high speed pulse input is sensitive to the external noise and should be handled with special care. When wiring the built-in 
high speed counter of MASTER-K120S, take the following precautions against wiring noise. 
 
(1) Be sure to use shielded twisted pair cables. Also provide Class 3 grounding. 
(2) Do not run a twisted pair cable in parallel with power cables or other I/O lines which may generate noise. 
(3) Before applying a power source for pulse generator, be sure to use a noise-protected power supply. 
(4) For 1-phase input, connect the count input signal only to the phase A input; for 2-phase input, connect to phases A and B. 
 