Toshiba 300kVA UPS Manuale Utente

Pagina di 1
Toshiba
 G8000 Series UPS 
Installation Planning Guide for 300kVA UPS 
Standard System: 480V Input, 480Y/277V Output 
Rev. 1.03 
Page 1 of 1 
G8000-IPG-300kVA 
 
General Mechanical Information 
Dimensions 
(W  x D x H) 
Weight 
Approximate Full-
Load Heat Loss 
Inches 
Lbs. 
Btu/Hr 
82.7 x 35.4 x 78.75 
4,630 
76,184 
 
Primary AC Input (480V 3-Phase / 3-Wire) 
Maximum Input Power 
Demand 
External Overcurrent 
Protection 
Suggested Minimum Feeder 
Wire Size – Per Phase  
Suggested Maximum Feeder Length 
For Min. Wire Size in Steel Conduit 
kVA 
PF 
Amps 
Amps 
AWG or kcmil at 75º C Temp. Rating 
Feet 
300 
>0.98 
361 
500 AT 
(2) x 4/0 
380 
 
Alternate (Bypass) AC Input (480V 3-Phase / 4-Wire) 
Maximum Input Power 
Demand 
External Overcurrent 
Protection 
Suggested Minimum Feeder 
Wire Size – Per Phase / Neutral
Suggested Maximum Feeder Length 
For Min. Wire Size in Steel Conduit 
kVA 
PF 
Amps 
Amps 
AWG or kcmil at 75º C Temp. Rating 
Feet 
300 
0.8 
361 
500 AT 
(2) x 2/0 / (2) x 350 
380 
 
Battery Input (360VDC Nominal) 
Battery Capacity Required 
for Full Load Output 
Maximum Discharge 
at Full Load Output 
External Overcurrent 
Protection 
Suggested Minimum Feeder 
Wire Size – Per Phase 
Suggested Maximum Feeder Length For 
Min. Wire Size in Steel Conduit 
kWB 
Amps DC 
Amps 
AWG or kcmil at 75º C Temp. Rating 
Feet 
255.3 
887 
1000 AT 
(2) x 4/0 
per battery cabinet
 70 
 
AC Output (480/277V 3-Phase / 4-Wire) 
Rated Output Power 
External Overcurrent 
Protection 
Suggested Minimum Feeder 
Wire Size – Per Phase / Neutral
Suggested Maximum Feeder Length 
For Min. Wire Size in Steel Conduit 
kVA 
PF 
Amps 
Amps 
AWG or kcmil at 75º C Temp. Rating 
Feet 
300 
0.8 
361 
500 AT 
(2) x 4/0 / (2) x 350 
380 
 
 
11.  Sizing calculations based on the following assumptions: 
-  Not more than 3 current-carrying conductors installed in steel 
conduit in ambient temperature of 30 degrees C. 
-  Temperature rating of conductors and terminals: 90 deg. C. 
- Feeder 
distance 
calculations based on NEC Tables 8 and 9 
data, allowing for 2% AC voltage drop. 
-  Reference: 2002 NEC Handbook. Consult latest edition of 
applicable national and local codes for possible variations. 
12.  Ratings of wires and overcurrent devices are suggested 
minimums.  Consult with a registered Professional Engineer 
within your local area for proper size selections. 
13.  More than one Battery Cabinet will require a DC Junction box 
for all battery cabinet connections. 
Important Notes: 
 
1.  Maximum Current required at Primary AC Input based on full 
load output and maximum battery charging current. 
2.  Output load conductors are to be installed in separate 
conduit from input conductors. 
3.  Control wires and power wires are to be installed in separate 
conduits. 
4.  Recommended AC input and output overcurrent protection 
based on continuous full load current per NEC. 
5.  Wiring shall comply with all applicable national and local 
electrical codes. 
6.  Grounding conductors to be sized per NEC Article 250-122.  
Neutral conductors to be sized per NEC Article 310.15. 
- Primary AC Input: 3
φ, 4-wire + ground. 
- Alternate AC Input: 3
φ, 4-wire + ground. 
- AC Output: 3
φ, 4-wire + ground. 
- DC Input: 2-wire (Positive/Negative) + ground. 
7.  Nominal battery voltage based on the use of VRLA type 
batteries (2.0 volts/cell nominal). 
8.  Maximum battery discharge current based on lowest 
permissible discharge voltage of 1.6 VPC. 
9.  DC wires should be sized to allow not more than a 2-volt 
drop at maximum discharge current. 
10. Weights do not include batteries or other auxiliary equipment 
external to the UPS. 
 