Home Automation 20A00-1 Manuale Utente

Pagina di 68
 
Page 52 
 
 
 
UNDERWRITER'S LABORATORIES (UL) INSTALLATION REQUIREMENTS 
 
The Omni II control units (20A00-1, -4, and -12) are suitable for Grade A household burglar and fire applications.  Refer to UL1641 for 
installation requirements.  Model 20A00-4 is also suitable for use in Commercial Burglar Alarm Applications, Grade B, C Central Station, 
Grade A Local, and Grade A Police Connect.  Refer to UL 681 for Installation Requirements. 
 
1. 
The line carrier (X-10) operation is considered supplementary.  Operation of the line carrier devices was not investigated by UL. 
 
2. 
For those zones programmed as PANIC, DURESS or POLICE EMERGENCY, the initiating device shall be a UL Listed Hold Up Device switch. 
 
3. 
Connections to phone circuit must be made via the supplied cable and RJ31X Jack as shown under RJ31X JACK CONNECTIONS in this manual. 
 
4. 
For connection of smoke detectors to the controller, refer to requirements under FIRE ZONE HOOKUP and FIRE ZONE CONNECTIONS diagrams in this 
manual. 
 
5. 
The controller must be configured for 24 hour Standby Time as shown under 24 HR STANDBY CONNECTIONS diagram in this manual.  Maximum 
current ratings for 24 hours must be observed. 
 
6. 
Recognized energy limited cable shall be employed, 22 AWG minimum for all connections. 
 
7. 
The audible signal appliance shall be the Listed Wheelock Model MT-12/24-R Multitone Signal, rated 10.5 - 15.6 VDC, 95 dB(A) with 2 reflecting planes. 
The audible signal shall be mounted indoors in a central location.  The audible signal appliance can be connected to either the "INT HORN" or "EXT 
HORN" circuits.  In the case of the latter, the OUTSIDE SIREN DELAY shall be set to 0 seconds. 
 
8. 
For Residential Applications, the Model 10A01-1 Enclosure shall be used. 
 
9. 
For Commercial Applications, the Model 10A02-2 Commercial Enclosure shall be used. 
 
10.  For Commercial Applications, Listed Ademco AB12 Bell and housing to be used. 
 
11.  If the remote arm/disarm switch is used, it shall be the Listed Ademco Model 9789. 
 
12.  Operation of the controls with the Programmable Energy Saver Module was not conducted by UL. 
 
13.  Operation of the Model 12A00 Wireless Receiver was not verified by UL. 
 
14.  Operation of the Two-Way Audio Module was not verified by UL. 
 
15.  RS-232 and RS-485 communications were not verified by UL. 
 
16.  Refer to the Omni II Owner's Manual (Document No. 20R00-1) for programming requirements in UL Listed Installations. 
 
 
 
17.  For the monitoring of burglar alarm initiating devices, the zone type shall provide an audible output (i.e., not DURESS). 
 
18.  The Omni controller must be connected (when employed) to listed carbon monoxide gas detectors (i.e. Sentrol -Model 240-CO). 
 
19.  All connections to energy sensors and modules must be done to listed Class 2 circuits only. 
 
20.  The Omni II must be used in Residential Applications that are under a single ownership. 
 
When used in UL Listed Installations, the following items apply: 
 
1. 
The "High Security Mode" must be ON. 
 
2. 
The "Enable Auto Bypass" feature must be OFF. 
 
3. 
The "Zone Resistors" must be YES. 
 
4. 
The "Supervise Int Horn" must be YES. 
 
5. 
The ENTRY DELAY SHALL NOT EXCEED 45 SECONDS for Residential Applications; 60 seconds for Commercial Applications. 
 
6. 
The EXIT DELAY shall not exceed 60 seconds. 
 
7. 
Double Delay and Quad Delay zone types shall not be used. 
 
8. 
The BEEP ON TROUBLE feature must be ON. 
 
9. 
For Residential Applications the sounding device may be mounted indoors.  If, however, the sounding device is connected to the "EXT HORN" terminals of 
the Omni II, then the OUTSIDE SIREN DELAY shall be set to 0. 
 
 
Installer:      NAME:  __________________________________            NUMBER:  _______________________________