ISACC Instruction Manual
remove the acrylic panel. Using needlenose pliers, move the shunt to the appropriate position.
See diagrams below. Replace the acrylic panel when finished.
See diagrams below. Replace the acrylic panel when finished.
TEMP position
- The default configuration connects the input signal to a 5V reference
through a 6.34K pull-up resistor. This configuration allows a thermistor, dry contact (N.C. or
N.O. ), or pulse counting sensor to be wired to the input. You may use either a 2.8K ther-
mistor or a 10K thermistor with ISACC.
N.O. ), or pulse counting sensor to be wired to the input. You may use either a 2.8K ther-
mistor or a 10K thermistor with ISACC.
P12
TEMP
4-20mA
1
Thermistor, dry contact or pulse count configuration
4-20mA position
- This configuration connects the input signal to a 249 Ohm load resistor.
This allows ISACC to measure the current at the input. Any sensor that puts out 4-20mA can
be wired to this input.
be wired to this input.
P12
TEMP
4-20mA
1
4-20mA configuration
0-5V (NO SHUNT) position
- This configuration connects the input signal directly to
ISACC’s analog to digital converter for measuring the output of 0 to 5 volt transducers. Any
sensor that puts out 0-5V can be wired to this input.
sensor that puts out 0-5V can be wired to this input.
P12
TEMP
4-20mA
1
0-5 Volt configuration
CAUTION: Wiring sensors with shunts in the incorrect position could result in
damage to the unit.
damage to the unit.