To wire the logic I/O (right side) to ISACC:
1.  Attach terminal 1 (on the right side) to 5 VDC on the ISACC power supply termi-
nal block.  Attach terminal 2 to one of the C (common) terminals on the ISACC
power supply terminal block.
2.  Connect an odd-numbered terminal (3, 5, 7, or 9) to one of the ISACC input
terminals (1-16) on the bottom row terminal block.  The shunt for this input must be
in the TEMP position.
To wire the field I/O (left side) to the input device:
If the input device is DC:
1.  Connect ground from the outside device to the odd-numbered terminal (3, 5, 7, or
9) on the rack.
2.  Connect the positive voltage from the outside device to the even-numbered termi-
nal (2, 4, 6, or 8) on the rack.
If the input device is AC, polarity does not matter and either wire can be connected to a
terminal pair on the rack.
See sample diagram below:
9
8
7
6
5
4
3
2
1
9
8
7
6
5
4
3
2
1
DC input
DC input
2I0-4A
LED
Solid state modules
AC input
AC input
DC device
+
G
DC device
+
G
AC device
AC device
Input devices
POWER
EG 24 24 BAT C 20V C
 
15V C
 
12V C 5V C
   AC AC
4-module rack
INPUTS
1
  2
  3
  4
  5
  6
  7
  8
  9 
10 
11 
12 
13 
14 
15 
16
Wiring AC and DC input modules using a 4-module rack
DIP CONNECTOR FOR A 16-MODULE RACK
If you need to use all 16 inputs for monitoring AC or DC voltage, you may simplify your
wiring by using a 16-module rack (Potter & Brumfield 2IO16), with a 50-pin  ribbon cable
with a card edge connector on one end and a 50-pin socket connector on the other end.  The
socket connector connects to the ISACC unit and the card edge connector connects to the