APC NBRK0570 Manuale Utente

Pagina di 152
40
NetBotz Appliance User’s Guide
Type the values in the appropriate fields. To see an example of an image capture using the updated 
settings, click Apply. The sample image in the Capture window is updated using the new values. When 
you are finished, click OK.
Post-Alert Capture Time
The total number of seconds after the alert generating event that 
images are included in alert notifications.
N
OTE
: For Pelco cameras, once an alert is generated a new alert 
will not be generated until 30 seconds has elapsed. To ensure that 
you capture all motion, set this field to 30 seconds.
The number of post-alert images captured is equal to the Post-Alert 
Capture Time multiplied by the Maximum Rate. If the total number 
of post-alert image captures and pre-alert image captures is larger 
than the Maximum Camera Pictures setting for an alert action, the 
most recent images captured are given preference and included in 
the alert notification.
Pre-Alert Capture Time
The total number of seconds prior to the event that generated the 
alert that images are included in the alert notification. The number 
of pre-alert images that are captured is equal to the Pre-Alert 
Capture Time multiplied by the Maximum Rate.
If the total number of post-alert image captures and pre-alert image 
captures is larger than the Maximum Camera Pictures setting for an 
alert action, the most recent images captured are given preference 
and included in the alert notification.
Delay Time Before Capturing
The number of seconds between when an alert is generated and the 
first picture capture. 
Include Audio
Specify whether the camera pod should capture audio and include it 
with the alert.
N
OTE
: This option is available only when configuring Capture 
settings for camera pods and CCTV Adapter Pods connected to a 
NetBotz 550, NetBotz 570 or an appliance with the Advanced 
Software Pack. 
Audio Volume
The volume at which audio is captured. 
Capture Data Summary 
Shows information about the files generated by the pod using the 
Capture settings. This information updates automatically as new 
settings are specified.
Field
Description