UDS1-BD (UDS1 Interface Circuit Pack)
Issue 1 June 2005
2449
 
When the test is complete, each trunk or port on the UDS1 Interface circuit pack is restored to 
the in-service state after the release board location command is entered.
Table 868: Test #1210 CSU Equipment Loop-Back Test 
Error
Code
Test
Result
Description / Recommendation
ABRT
Internal system error
1. Retry test ds1-loop location ds1/csu-loopback-tests at 
1-minute intervals up to 5 times.
1005
ABRT
CSU Equipment Loopback test cannot be executed in the current 
configuration. To run this test, the Near-End CSU Type field on the DS1 
circuit pack administration screen must be set to integrated and the Bit 
Rate
 field on the DS1 circuit pack administration screen must be set to 
1.544 (24-channel configuration).
1. Use change ds1 location to set the Near-End CSU Type field on 
the DS1 circuit pack administration screen to integrated, and/or 
change the Bit Rate field to 1.544 if the board is to be used in 
24-channel configuration.
2. Retry test ds1-loop location ds1/csu-loopback-tests.
1015
ABRT
Ports on the UDS1 Interface circuit pack have not been busied out to 
out-of-service.
1. Enter busyout board location to put every trunk or port of the 
UDS1 Interface circuit pack into the out-of-service state.
2. Retry the command.
1039
ABRT
The UDS1 Interface circuit pack is providing timing for the system. 
Executing this test could cause major system disruption.
If the UDS1 Interface circuit pack needs to be tested, set the 
synchronization reference to another DS1 Interface circuit pack or to the 
IPSI or Tone-Clock circuit pack via the following command sequence:
1. Enter disable synchronization-switch.
2. Enter set synchronization location.
3. Enter enable synchronization-switch.
Rerun the test. If the test aborts again, a different ABRT code will be 
generated. Follow the recommended maintenance procedures for the Error 
Code. 
 1 of 3