Communication Manager Maintenance-Object Repair Procedures
544 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
 
z. Aux Data 32767 for any error log entry indicates that an alarmed ATM-EI was busied out 
and then released.  When this occurs, existing service-affecting alarms must be preserved.  
Typically, every alarm is resolved when the ATM-EI is released.  Therefore, the Alarm and 
Error Logs must be repopulated with the alarms present at time of busyout.  This Aux Data 
indicates that existing Error Type and Error Log time stamps are no longer valid because 
they were lost when the circuit pack was released.
System Technician-Demanded Tests:
Descriptions and Error Codes
Investigate tests in the order presented. By clearing error codes associated with the Expansion 
Interface 2-Way Transmission test (#241), you can also clear errors generated from other tests 
in the sequence.
Note:
Note:
To get a better indication of a problem’s location, test both ATM-EI circuit packs 
on the associated fiber link, whether the circuit packs are both ATM-EI circuit 
packs or not.
Table 173: System Technician-Demanded Tests: ATM-EI 
Order of Investigation
Short Test 
Sequence
Long Test 
Sequence
Reset 
Board 
Sequence
D/
ND
1
1. D = Destructive, ND = Nondestructive
Expansion Interface 2-Way Transmission 
test (#241)
X
X
ND
ATM Board Framer Looparound test (#1260)
X
D
Expansion Interface Lock Query test (#304)
X
X
ND
ATM Board Error Query test (#1259)
X
X
ND
ATM Expansion Interface Reset (#1256)
X
D
ATM board DSP test(#1293) for TN2305 and 
TN2306 circuit packs.
X
X
ND
ATM Cross Talk test(#1298) for TN2305 and 
TN2306 circuit packs
X
ND