Bosch LTC 9440 Manuale Utente

Pagina di 96
 
Caution: Do Not Exceed 30 VAC Input on  
24 VAC models. Operation above 30 VAC 
violates low voltage operation (Class 2 
Specifications). Normal operation is 24 VAC. 
CUL Approved 24 VAC Models. 
 
Caution: Connect to Class 2 Power Supply 
only. Total current through electrical 
connector is 4 A maximum. Pan/tilt current 
is 1 A maximum. Allowable camera/housing 
is 3 A maximum. Use only 24 VAC cameras 
and housings on feed-through models. 
 
3.2 
Recommended Mounting Equipment 
LTC 9216/00 
Medium duty wall mount designed to 
support up to 45.3 kg (100 lb). 
LTC 9222/00 
Heavy duty wall mount designed to 
support up to 90.6 kg (200 lb). 
LTC 9214/00 
Heavy duty 336 mm (14 inch) column 
mount for ceiling or pedestal. 
LTC 9224/00 
Heavy duty 610 mm (24 inch) column 
mount for ceiling or pedestal use. 
3.3 Wall 
Mounting 
Follow the instructions provided with mounts. Mount and 
mounting surface must be able to support the weight of the 
pan/tilt, camera/lens, and enclosure (if used).  The 
camera/lens/enclosure must be properly mounted and 
balanced on the pan/tilt bracket. 
Caution: The pan/tilts can only be mounted 
upright or inverted; never horizontally. 
 
3.4 Camera/Lens/Enclosure 
Mounting 
Mount the camera/lens/enclosure to the pan/tilt bracket as 
follows: 
1.  Balance the camera/lens/enclosure and adjust unit to 
align with mounting holes. Fasten with a minimum of two 
(2) 1/4-20 x 1/2-inch long fasteners and lock washers. 
2.  Make all electrical connections. Leave sufficient loops of 
cable between camera/enclosure and pan/tilt to allow for 
tilting and panning. 
3.5 Electrical 
Connections 
1.  Cable must be wired according to Connector 
Assembly (Section 3.7) and Recommended 
Maximum Cable Lengths 
(Table 1). 
2.  Use separate shielded cables for camera power, 
enclosure power, and pan/tilt control. If required, 
combining lens control wiring and video coax within a 
common cable is acceptable. The use of a common 
multiconductor cable to combine all functions is not 
recommended. 
3.  Use color coded conductors to aid wiring and future 
identification. 
4.  Retain wiring diagram for later reference. 
Model Wire 
Size  Distance
1
 
Voltage Mm
2
 AWG Feet 
Meters 
24 VAC
2
 0.5 
20  140 
43 
 1 
18 
230 
70 
 1.5 
16 
360 
110 
 2.5 
14 
590 
180 
 4 
12 
940 
287 
110 VAC 
0.5 
20 
2200 
671 
 1 
18 
3500 
1067 
 1.5 
16 
5500 
1677 
 2.5 
14 
9000 
2744 
220 VAC 
0.5 
20 
13400 
4085 
 1 
18 
21200 
6463 
 1.5 
16 
33300 
10152 
 2.5 
14 
54400 
16585 
 
Table 1      Maximum Cable Lengths 
 
Notes For Table 1 
1. 
Values calculated at 20 ºC (68 ºF) using stranded tinned copper 
wire, a common ground (neutral), and with both PAN and TILT 
motors operating simultaneously. 
2. 
For 24 VAC Models operating at or near -30º C, values are based 
upon maintaining the supplied voltage within the voltage range as 
specified in Section 3.1. 
AMP Hand Crimping Tool #58495-1 is recommended for 
crimping sockets. Refer to Figure 2 for the numbered 
connector positions.The connector will accept up to a #16 
AWG wire. If heavier gauge wire is required, pigtailing 
according to local electrical codes is recommended. 
Caution: Contact removal from connector 
requires use of AMP #305183 extraction 
tool. 
3.6 Grounding 
Connection 
A ground screw is located on the base to the right of 
connector. See Figure 8. Connect a 1 mm
2
 (No.18 AWG) 
ground wire to the nearest earth ground. 
3.7 Connector 
Assembly 
A mating connector, sockets and a strain relief are included 
with the unit. See Figure 1
To install, select the appropriate size strain relief clamp.  
Choose one of the two strain relief clamps enclosed with the 
sleeve and the extender. The clamping area is adjustable by 
inverting or changing the strain relief clamps. Discard the 
four strain reliefs on the carrier strip packaged with the 
shield. 
Insert the clamp into the strain relief until it bottoms. The 
clamp should bottom on the wire bundle, not on the shield’s 
shoulder. If the wire diameter is too small, temporarily 
wrap the wire with electrical tape until proper clamping is 
obtained. Secure the clamp with the two (2) screws 
provided.  
Caution: Make sure the wire bundle is 
properly secured. Do NOT pinch the wires.