CONTROL CONFIGURATION
KEYBOARD
ENTRY
DISPLAY
DESCRIPTION
VALUES IN [
] INDICATE FACTORY DEFAULTS
LOG ON
Enter password followed by
ENTER
LOGGEDON
Logged on okay
FACT CFG
Factory configuration
TYPE X
Unit type (0 = CV, 1 = VAV) [Default is 1]
ENTER
x
TYPE X
Verify unit type and change if necessary. If CV unit, see CV
control configuration.
DTRS
Data Reset
Enable Data Reset
ENTER
FACT CFG
Factory Configuration
LLAG X
Use
to access lead/lag option — disable with
HGBP (Item D, page CL-1)
ENTER
DISABLE
Disable lead/lag (0 = DIS, 1 = ENB) [1]
BLD PRES
Configure building pressure control (modulating power
exhaust)
BPS .05
Use
for building pressure set point (range 0 to .5) [.05]
ENTER
x
BPS X
Set building pressure set point per job requirements
LOGGEDON
Access log on/off function
LOG OFF
Use
to access log off
ENTER
LOGD OFF
Logged off okay
INPUTS
Run quick test to verify operation of unit functions
(see Controls and Troubleshooting Guide)
through
SETPOINT
Set system set points per job requirements
OHSP X
Set occupied heat set point (Range 55-80 F) [68] CV only
OCSP X
Set occupied cool set point (Range 55-80 F) [78] CV only
UHSP X
Set unoccupied heat set point (Range 40-80 F) [55]
UCSP X
Set unoccupied cool set point (Range 75-95 F) [90]
SPSP X
Set supply duct pressure set point (Range 0-5.0 in. wg) [1.5]
SASP X
Set supply air set point temperature (Range 45-70 F) [55]
TIME
Current time/date
dow.hh.mm
Set day of week and time
mm.dd.yy
Set month, day, and year
DAYLIGHT
Set daylight savings time begin/end dates. Required if job
conditions require adjustment of clock for daylight savings time
(see Controls and Troubleshooting Guide)
HOLIDAY
Set holiday dates. Required if job conditions require a different
schedule on holidays than other days (see Controls and Trouble-
shooting Guide)
PERIOD X
Set occupied/unoccupied schedules. Required if job condi-
tions require unit to enter unoccupied cycle at programmed
times of day or days of week (see Controls and Troubleshoot-
ing Guide)
through
NOTE: Data in brackets [
] is default value.
CL-3