EYF Series Unvented Gas Log Set
INSTALLATION
Heat resistant material (minimum requirements) with 
wooden  mantel  or  other  combustible  projection:
  To 
install  the  heater  with  a  wooden  mantel,  shelf  or  other 
combustible  projection  above,  first  measure  the  heat 
resistant material shown in Figure 6, then refer to Table 
B.
FP2532
mantel clear w hood
8" or More of Heat 
Resistant Material
Hood
Heater in 
Fireplace or 
Firebox
FP53
Figure 6 -
Mantel Clearance with Hood
 
 
EYF24/18 Requirements   
 
 
for Safe Installation with   
 Heat Resistant Material  Wooden Mantel, Shelf or   
 
Measurement 
Other Combustible  
 
 
 
Projection
  0" or more 
Hood not required. Figure 6 
  8" to less than 0" 
Install hood (CABR/CABL)  
 
   
and refer to Figure 7OR 
 
   
extend heat resistant material  
   
to at least 1" and refer to 
 
   
Figure 8.
  Less than 8" 
Extend heat resistant material  
   
to at least 8" and install hood 
   
(CABR/CABL), refer to  
 
   
Figure 6. OR, extend heat  
 
   
resistant material to a height   
   
of at least 1" and refer to 
 
   
Figure 8.
Table B - 
Heat Resistant Material Heights and Mantel Location
8” 
Min
13”
18”
20”
256O”
6” - 10”
12”
FP2534
Min. mantel w hood
Heat 
Resistant 
Material
Hood
Heater in Fireplace 
or Firebox
FP534
Figure 7 - 
Minimum Mantel Clearance with Hood
Example:   A mantel may project from the wall a maximum 
of Z\x" at a minimum of  13" above the opening and a 
maximum of 10" at a minimum of 18" above the open-
ing. 
20”
Min.
32”
10” or Less
FP2535
min mantel no hood
Heat 
Resistant 
Material
Heater in Fireplace 
or Firebox
FP535
Figure 8 - 
Minimum Mantel Clearance with No Hood
Example:   The bottom of the mantel may project from the 
wall a maximum of 10" at a minimum of 3" above the 
opening.