Heatcraft Refrigeration Products H-IM-CU Manuale Utente

Pagina di 24

Requirements for Remote and Water Cooled
Condensing Units
General Installation
The indoor compressor units are designed to be used with a remote 
condenser.  The water cooled units are similar, except that they have an 
integral water cooled condenser. Inlet and outlet water connections are to 
be made in the field.  On units having a compressor water jacket, incoming 
water shall be routed through the jacket prior to entering the condenser.  For 
cleaning purposes, condenser end plates can be removed to give access to 
the water tubes.  Cleaning is accomplished by a simple spiral tool powered 
by an ordinary electric drill.  During installation, allow space for cleaning the 
condenser.  Commercial equipment of this type is intended for installation 
by qualified refrigeration mechanics.   
Typical Arrangements
Diagram 1 illustrates a typical piping arrangement involving a remote 
condenser located at a higher elevation, as commonly encountered when 
the condenser is on a roof and the compressor and receiver are on grade 
level or in a basement equipment room.
In this case, the design of the discharge line is very critical.  If properly sized 
for full load condition, the gas velocity might be too low at reduced loads 
to carry oil up through the discharge line and condenser coil.  Reducing the 
discharge line size would increase the gas velocity sufficiently at reduced 
load conditions; however, when operating at full load, the line would be 
greatly undersized, and thereby creating an excessive refrigerant pressure 
drop.  This condition can be overcome in one of two of the following ways:
 The discharge line may be properly sized for the desired pressure  
 
 
drop at full load conditions and an oil separator installed at the  
 
 
bottom of the trap in the discharge line from the compressor.
1.
City & Tower Water Connections
In the refrigeration industry “City” and “Tower” are designations of 
temperature and flow conditions, not applications.  The term “City” refers 
to operating conditions where incoming water is 75˚F, and condensing 
temperature is 105˚F. “Tower” refers to a higher temperature relationship 
which is normally 85˚F, incoming water and 105˚F condensing temperature.
Water circuits in some condenser models provide a center, or Tower, outlet 
connection to allow divided inlet water flow. This extra water port reduces 
water velocity, water pressure drop, and condenser wear in applications such 
as cooling towers where higher inlet temperatures and water flows occur.
Water Connections for City
For City water (open system) high pressure applications, the Tower 
connections is plugged.
Water Connections for Tower
For Tower usage and low pressure applications, both normal water 
connections will be used as inlets and the tower connection as an outlet.
Diagram 1
Diagram 2
Figure 2. Water Connections
A double riser discharge line may be used as shown in  
 
 
 
Diagram 2.  Line “A” should be sized to carry the oil at minimum  
 
 
load conditions and the line “B” should be sized so that at the  
 
 
full load conditions both lines would have sufficient flow velocity  
 
 
to carry the oil to the condenser.
Water Regulating Valve
Using this control on the water cooled condensing units, the head pressure 
can be maintained by adjusting the flow of water through the condenser 
section.  This type control is most often located on the water entering side of 
the condenser and is regulated by the refrigerant condensing pressure.
Subcooler
Diagrams 1 and 2 below show typical subcooler piping.  Diagram 1 is the 
preferred connection with receiver as it provides maximum subcooling.  
Diagram 2 may be used if the receiver is located far from the condenser.
Notes:
All oil traps are to be as short in radius as possible. Common practice is   
 
to fabricate the trap using three 90 degree ells.
Pressure relief valves are recommended at the condenser for protection  
 
of the coil. 
A pressure valve at the high point in the discharge line is recommended  
 
to aid in removing non-condensables.
The placement of a subcooler should be that it does not interfere with    
 
normal airflow of the condenser. Increased static of the unit could cause  
 
a decrease in system capacity and fan motor damage.
2.
1.
2.
3.
4.