EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE  
 
 EN2B-0285GE51 
R0909 
13
 
Fig. 9. Three-speed fan switching and hysteresis, cooling mode (defaults for switching levels shown) 
 
 
Type of Heating and Cooling Equipment 
Excel 10 FCU Controllers can operate with either two-pipe or 
four-pipe systems. A two-pipe system requires a changeover 
input to the controller (hardware or network input). 
 
Excel 10 FCU Controllers can operate with a variety of 
actuators for heating and cooling equipment. Floating 
actuators can be used; this requires that the valve run time be 
specified during configuration of the controller. 
 
The actuator runtimes can be configured in the range 20 sec 
to 600 sec in steps of 1 second. 
 
Valves will be synchronized by driving the valve fully closed 
(150% of the valve run time) under the following conditions: 
 
•  whenever the control level reaches 0% or less; 
• at 
power-on; 
•  whenever the occupancy status changes to a lower mode, 
e.g., from occupied to standby or unoccupied; 
•  when synchronization has not taken place within the last 
24 hours. 
 
Once synchronization has been completed, the output control 
will be returned to the normal control loop. 
 
Valve action can be configured as either direct or reverse. 
When in a two-pipe system with a changeover input, a floating 
actuator can be used which has the middle position (50%) as 
the zero energy position. The cool range is then 0 to 50% and 
the heat range 50 to 100%. The output must be configured as 
floating-mid. 
 
Multi-stage systems can be controlled with up to three 
different stages of heating/cooling control. Switching levels 
are specified in % of control level (see Fig. 10) as is a 
hysteresis setting which applies to all switching levels. 
Heating and cooling switching levels and hysteresis are 
specified separately. Min. OFF times can be configured, and 
for one-, two- and three-stage systems, a min. ON time can 
also be configured. 
 
PWM electronic valves and thermal actuators can also be 
connected and can be configured as either direct or reverse 
action. The cycle time must be specified during configuration. 
In the case of PWM valves, the zero and full positions must 
also be configured. 
 
Additionally, the W7754K1001 features an extra socket 
(located to the left of the terminal blocks) containing a digital 
output suitable for connection to a solid-state relay employed 
for low-voltage PWM control in high-current electric reheat 
applications.