EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE 
EN2B-0285GE51 R0909 
28
Equipment Control 
The available options for equipment control configurations with the default values shown are listed in the following table. See 
section "Configurations" on page 12 for more information about parameters. 
 
Table 18. FCU Controller equipment control configuration options 
function 
configuration options 
default 
output 1 fan interlock 
enabled / disabled 
disabled 
output 2 fan interlock 
enabled / disabled 
disabled 
output 1 valve direction
1
 
direct / reverse 
direct 
output 2 valve direction
1
 
direct / reverse 
direct 
output 1 min. stage OFF time 
0 to 600 seconds 
90 s 
output 2 min. stage OFF time 
0 to 600 seconds 
90 s 
output 1 valve run time/PWM 
period/min. stage ON time 
floating - valve run time (20 to 600 seconds) 
PWM - cycle time (20 to 600 seconds) 
1, 2, and 3-stage – min. ON time (0 to 1200 seconds) 
150 s 
output 2 valve run time/PWM 
period/min. stage ON time 
floating - valve run time (20 to 600 seconds) 
PWM - cycle time (20 to 600 seconds) 
1, 2, and 3-stage – min. ON time (0 to 1200 seconds) 
150 s 
reheat switching level 
0 to 100% 
100% 
reheat hysteresis 
0 to 100% 
5% 
PWM zero position
2
 
0 to 100% 
0% 
PWM full position
2
 
0 to 100% 
100% 
 Notes: 
 
1. Valve action settings apply to floating, PWM, or thermal types. 
 
2. Settings apply to both actuators if both are PWM. 
 
 
Fan 
Available options for fan control are listed in the following table. See section "Configurations" on page 12 for more information 
about parameters. 
 
Table 19. FCU Controller fan configuration options 
function 
configuration options 
default 
fan occupancy mode 
continuous during occupied mode; 
automatic, based on control algorithm 
automatic 
fan min. ON time
1
 
0 to 1200 seconds 
fan min. OFF time
1
 
0 to 1200 seconds 
fan run-up time
1
 
(with fan interlock only) 0 to 600 seconds 
fan overrun time
1
 
(with fan interlock only) 0 to 600 seconds 
 Notes: 
 
1. Fan run time options apply to all fan speeds.