Lindy 19" Rackmount Power Meter 32710 Manuale Utente
Codici prodotto
32710
LINDY Part No. 32710 SNMP Settings
gadsEPM
subtree name
OID
description
r /
w
w
GUDEADS-EPM-MIB 1.3.6.1.4.1.28507
Gude Analog- und
Digitsysteme GmbH MIB
(Private Enterprise)
Digitsysteme GmbH MIB
(Private Enterprise)
r
GUDEADS-EPM-
MIB::gadsEPM
MIB::gadsEPM
1.3.6.1.4.1.28507.2
Expert Power Meter MIB
r
chanActive
1.3.6.1.4.1.28507.2.1.1
How many power channel
are active
are active
r
chanTable
1.3.6.1.4.1.28507.2.1.2
Expert Power Meter
Channel SMI-Table
Channel SMI-Table
r
chanEnergyTotal
1.3.6.1.4.1.28507.2.1.2.1.2
Total accumulated energy
of power channel
of power channel
r
chanEnergyTotalReset 1.3.6.1.4.1.28507.2.1.2.1.3
Total (resettable)
accumulated energy of
power channel
accumulated energy of
power channel
r
chanEnergyActive
1.3.6.1.4.1.28507.2.1.2.1.4 Real active Energy (Watt) r
chanEnergyApparent
1.3.6.1.4.1.28507.2.1.2.1.5
Active Apparent Energy
(VA)
(VA)
r
chanCurrent
1.3.6.1.4.1.28507.2.1.2.1.6
Actual Curent on Power
Channel (milliAmpere)
Channel (milliAmpere)
r
chanVoltage
1.3.6.1.4.1.28507.2.1.2.1.7
Actual Voltage on Power
Channel (Volt)
Channel (Volt)
r
system
interface
gadsepm
system und interface are standardised MIBs (MIB-II), gadsepm is in a MIB (GUDEADS-EPM-
MIB::gadsEPM) especially designed for Expert Power Meter. Subordinated to these three
structural branches are the OIDs (Object Identifiers). An OID position stands for the location
of a value within the MIB structure. Every OID can alternatively be identified by its symbolic
name (subtree name).
system
subtree name OID
system 1.3.6.1.2.1.1
sysDescr 1.3.6.1.2.1.1.1
sysObjectID 1.3.6.1.2.1.1.2
sysUpTime 1.3.6.1.2.1.1.3
sysContact 1.3.6.1.2.1.1.4