Lindy 19" Rackmount Power Meter 32710 Manuale Utente

Codici prodotto
32710
Pagina di 10
LINDY Part No. 32710 SNMP Settings
 
 
gadsEPM 
subtree name  
OID  
description  
r / 
w  
GUDEADS-EPM-MIB   1.3.6.1.4.1.28507  
Gude Analog- und 
Digitsysteme GmbH MIB 
(Private Enterprise)  
r  
GUDEADS-EPM-
MIB::gadsEPM  
1.3.6.1.4.1.28507.2  
Expert Power Meter MIB  
r  
chanActive  
1.3.6.1.4.1.28507.2.1.1  
How many power channel 
are active  
r  
chanTable  
1.3.6.1.4.1.28507.2.1.2  
Expert Power Meter 
Channel SMI-Table  
r  
chanEnergyTotal  
1.3.6.1.4.1.28507.2.1.2.1.2  
Total accumulated energy 
of power channel  
r  
chanEnergyTotalReset   1.3.6.1.4.1.28507.2.1.2.1.3  
Total (resettable) 
accumulated energy of 
power channel  
r  
chanEnergyActive  
1.3.6.1.4.1.28507.2.1.2.1.4   Real active Energy (Watt)   r  
chanEnergyApparent  
1.3.6.1.4.1.28507.2.1.2.1.5  
Active Apparent Energy 
(VA)  
r  
chanCurrent  
1.3.6.1.4.1.28507.2.1.2.1.6  
Actual Curent on Power 
Channel (milliAmpere)  
r  
chanVoltage  
1.3.6.1.4.1.28507.2.1.2.1.7  
Actual Voltage on Power 
Channel (Volt)  
r  
 
 
system  
interface  
gadsepm  
system und interface are standardised MIBs (MIB-II), gadsepm is in a MIB (GUDEADS-EPM-
MIB::gadsEPM) especially designed for Expert Power Meter. Subordinated to these three 
structural branches are the OIDs (Object Identifiers). An OID position stands for the location 
of a value within the MIB structure. Every OID can alternatively be identified by its symbolic 
name (subtree name).  
 
 
system 
subtree name  OID   
system  1.3.6.1.2.1.1   
sysDescr  1.3.6.1.2.1.1.1   
sysObjectID  1.3.6.1.2.1.1.2   
sysUpTime  1.3.6.1.2.1.1.3   
sysContact  1.3.6.1.2.1.1.4