The appliance, when installed, must be electrically grounded in ac-
cordance with local codes or, in the absence of local codes, with the 
National Electrical Code, ANSI/NFPA 70 or Canadian Electrical 
Code, CSA C22.1, if an external electrical source is utilized. This 
appliance is equipped with a three-prong [grounding] plug for 
your protection against shock hazard and should be plugged 
directly into a properly grounded three-prong receptacle. Do 
not cut or remove the grounding prong from this plug. For an 
ungrounded receptacle, an adapter, which has two prongs and a 
wire for grounding, can be purchased, plugged into the ungrounded 
receptacle and its wire connected to the receptacle mounting screw. 
With this wire completing the ground, the appliance cord plug can 
be plugged into the adapter and be electrically grounded. A 7/8” 
hole is provided in the junction box for use with a conduit connector 
if local codes require this type of protection.
Thermostat Installation
The thermostat should be installed in the same room as the furnace 
4’ to 5’ above the floor and away from another heat source (cooking 
stove, hot water heater, etc.) including walls and doorways with 
a heat source in an adjoining room. Do Not Install Thermostat 
on Outside Wall.
CAUTION:  Label  all  wires  prior  to  disconnection  when 
servicing  controls.  Wiring  errors  can  cause  improper  and 
dangerous operation. Verify proper operation after servicing.
Figure 14
The correct flame will be a short, blue inner flame with a much 
larger, light blue, outer flame. The burner does not have a primary 
air adjustment. The flame will be correct if the factory-set pressure 
and orifice opening are used. After the furnace has been operating, 
the burner ports may be blocked by foreign matter carried in by 
combustion air. Therefore, cleaning of the burner may be needed 
for proper flame.
To clean burner port disconnect the gas supply to the valve, and 
remove the screws fastening the burner door. After removing the 
burner door from the burner box, remove each main burner. Pilot 
mounting bracket will need to be unscrewed and moved out of the 
way to remove all burners. Burners can be blown out using com-
pressed air or by blowing through them. Be sure there is no lint 
or foreign debris blocking the burner ports. Reassemble using the 
same screws earlier removed and locate pilot in the same position 
as before and noted above. 
Figure 13
DVC-35T
DVC-35IPT
MAIN BURNER FLAME CHARACTERISTICS
WIRING