Empire Products GWT-35-2 Manuale Utente

Pagina di 20
12425-7-0406
Page 11
THERMOSTAT LOCATION (SG MODELS)
CAUTION — Do not run wire behind flanges of Header Plate 
or in any location where it might be damaged.  
Millivolt wall thermostats are specially designed for use on self-
generating systems.  They should never be used on line or low 
voltage A.C. circuits.
Interior Wall — The thermostat should be installed on an inside 
wall away from the furnace but in the same room.  
Note:    Use  16  gauge  wire  to  prevent  excessive  loss  of  milli-
volts.
Proper operation depends on a good pilot flame.  The flame must 
cover the top of the thermopile.  Cleaning of the pilot orifice and 
burner may be required due to spiders.
System Check (Figure 7)
A  millivolt  meter  is  required  to  check  the  system.    Millivolt 
readings should be:
•  Across  the  thermopile  terminals,  400-450  millivolts  with  
thermostat OFF.
•  Across  the  thermopile  terminals,  150-250  millivolts  with  
thermostat ON.
•  Across the thermostat wires at the valve, less than 30 millivolts 
with  thermostat ON.
•  Across  the  thermostat  wires  at  the  thermostat,  less  than  5 
millivolts with thermostat ON.  (Dirty pilot or low pressure 
will reduce readings.)
Connect thermostat wires to gas valve as shown in Figure 7.
Figure 7