GENERAL      All  furnaces  have  been  fire-tested  to  check  for 
proper operation.  This includes main burner flame, pilot flame, 
and gas control operation.  If the furnace fails to function on initial 
installation, it is advisable to re-check the following: 
1.  Inlet gas pressure.
2.  Type  of  gas  being  used  and  that  shown  on  the  rating 
plate.
The Service Department at Empire Comfort Systems, Inc. may be 
contacted to assist in servicing furnace.
Servicing the Pilot and Main Burner, Pilot Orifice, Thermopile 
and Main Burner Orifice  
Disconnect  the  gas  supply  at  the  inlet  to  the  control  valve.   
Remove  the  burner  assembly  to  which  the  above  components 
are attached.
Pilot Does Not Light 
With air in the gas line, such as when the furnace is first installed 
or  was  "OFF"  all  summer,  the  pilot  flame  may  be  too  lean  to 
ignite on the first few trials.  Turn the gas control knob to PILOT 
position and depress the gas control knob.  Hold the gas control 
knob down to bleed the line;
1.  Use lighter rod to light pilot with a match.
If Pilot Does Not Light By Any Means 
1.  Check gas control knob for being in the "Pilot" position.
2.  Check pilot adjustment for being full open (counterclockwise 
to open).
3.  If gas is available in the supply tubing, the pilot orifice 
and/or pilot burner is probably restricted by a spider web.  
Clean pilot assembly and relight.
If Pilot Does Not Remain "On" After Releasing Gas Control 
Knob 
1.  Follow instructions and hold gas control knob down longer 
and harder.
2.  Determine if pilot flame extends past thermopile; if not, 
adjust pilot flame or clean pilot burner.
3.  Replace thermopile if millivolt reading is less than 300 
millivolts when wall thermostat or remote bulb is turned 
OFF.   Replace gas control if magnet dropout millivolt 
reading is over 100 millivolts.
Pilot Outage During Normal Operation
1.  Check input by manifold pressure gauge or gas meter.
2.  Check millivolt output when furnace is in operation.  If 
millivolt output decreases during furnace operation gas 
control may be defective. 
Main Gas Valve Does Not Open When Thermostat Is Turned 
"On" 
1.  Check millivolt output of thermopile.
2.  Thermostat wires may be broken.
3.  Thermostat may be defective. 
TROUBLESHOOTING