Cal Flame Side Burners
LTR50001082, Rev. B
www.calspas.com
LP Gas
Tank Requirements
For plumbed-in LP installation, use a convertible regulator and set it 
for LP gas. 
Maximum line pressure for plumbed-in propane is 14” WC (3.5 kPa). 
Minimum line pressure for propane is 11” WC.
The side burner unit must be used with the gas pressure regulator. The 
regulator will control and maintain a uniform gas pressure in the mani-
fold. The burner orifices have been sized for the gas pressure delivered 
by the regulator.
WARNING: Attempting to operate the side burner unit without the 
gas regulator installed could cause an explosion and possible death.
Cylinder Specification
Any LP gas supply cylinder used with this side burner must be:
Constructed and marked in accordance with the 
• 
Specifications 
for LP-Gas Cylinders of the U.S. Department of Transportation 
or  the  National  Standard  of  Canada,  CAN/CSA-B339,  Cylin-
ders, Spheres and Tubes for Transportation of Dangerous 
Goods; and Commission, as applicable.
Approximately 12 inches in diameter and 18 inches high.
• 
The maximum fuel capacity is 20 lbs. of propane, or 5 gallons.  Full cyl-
inder weight should be approximately 38 lbs. (43.7 lbs. nominal water 
capacity.) Never fill the cylinder beyond 80% full.