Caution to conform with EC Directives
• Installation in Enclosure
Programmable logic controllers are open-type devices that must be installed and
used within conductive control cabinets. Please use the programmable logic
controller while installed within a conductive shielded control cabinet. Please secure
the cabinet door to the control cabinet (for conduction).
Installation within a control cabinet greatly affects the safety of the system and aids
in shielding noise from the programmable logic controller.
used within conductive control cabinets. Please use the programmable logic
controller while installed within a conductive shielded control cabinet. Please secure
the cabinet door to the control cabinet (for conduction).
Installation within a control cabinet greatly affects the safety of the system and aids
in shielding noise from the programmable logic controller.
• Control cabinet
- The control cabinet must be conductive.
- Ground the control cabinet with the thickest possible grounding cable.
- To ensure that there is electric contact between the control cabinet and its door,
- Ground the control cabinet with the thickest possible grounding cable.
- To ensure that there is electric contact between the control cabinet and its door,
connect the cabinet and its doors with thick wires.
- In order to suppress the leakage of radio waves, the control cabinet structure must
have minimal openings. Also, wrap the cable holes with a shielding cover or other
shielding devices.
shielding devices.
- The gap between the control cabinet and its door must be as small as possible by
attaching EMI gaskets between them.
*1. These wires are used to improve the conductivity between the door and control
cabinet.
Shielding cover
Shielded cable
Wires*1
EMI gasket