MELSEC-F
FIXED BUFFER COMMUNICATION (WITH THE NO PROCEDURE 
CONTROL METHOD)
7
7 - 11
(b) Receive program (FX
3U
 -2nd station)
1) Connection No. 2 is used to process the fixed buffer receiving.
2) The unit number specified at the sequence program and 
 
FX Configurator-EN-L is 0.
3) Make Operation settings in the following manner.
Communication data code : Binary code
Initial timing
: Do not wait for OPEN (Communications 
impossible at STOP time)
Local station IP address
: 10.97.85.223 (0A.61.55.DF
H
4) Adjust open settings in the following manner.
Protocol
: TCP
Open system
: Fullpassive
Fixed buffer
: Receive
Fixed buffer communication procedure
: No procedure exist (BFM#33 b9 : ON)
Pairing open
: Disable (BFM#33 b7 : OFF)
Existence confirmation
: No confirm (BFM#33 b1 : OFF)
Local station Port No.
: 8192 (BFM#47)
5) Fixed buffer No.1 receive data.
 
: Stored in D1000 to D1031
6) Fixed buffer No.1 receive instruction complete status.
 
: D100
[Operational settings]
[Open setting]
Setting name
Settings in FX Configurator-EN-L
Settings in the program
Communication data code setting
Binary code
BFM#24 b1:OFF
Initial timing
Always wait for OPEN 
 
(Communications impossible at STOP time)
BFM#24 b8:ON
Local station IP address
10.97.85.223 (0A.61.55.DF
H
)
BFM#106 to 108
Send frame setting
Ethernet (V2.0)
BFM#24 b5:OFF
TCP Existence confirmation setting Use the Ping
BFM#24 b4:OFF
Setting name
Settings in FX Configurator-EN-L (No.2)
Settings in the program
protocol
TCP
BFM#33 b8:OFF
Open system
Fullpassive
BFM#33 b14,b15:10
Fixed buffer
Receive
BFM#33 b0:ON
Fixed buffer communication
No procedure
BFM#33 b9:ON
Paring open
No pairs
BFM#33 b7:OFF
Existence confirmation
No confirm
BFM#33 b1:OFF
Local station Port No.[Decimal]
8192
BFM#47
Destination IP address
10.97.85.222 (0A.61.55.DE
H
)
BFM#48,49
Destination Port No.[Decimal]
4096
BFM#50
POINT
Make sure to have sufficient device memory according to the maximum data 
length  sent in order to prevent device areas used for other purposes from being 