C7027A, C7035, C7044A, C7927A MINIPEEPER® ULTRAVIOLET FLAME DETECTORS
60-2026—11
4
Fig. 4. Installation dimensions of C7927A1016 (U.S.A. version) and C7927A1008 (European version) in in. (mm).
INSTALLATION
When Installing This Product...
1. Read these instructions carefully. Failure to follow 
them could damage the product or cause a hazardous 
condition.
2. Check the ratings given in the instructions and on the 
product to make sure the product is suitable for your 
application.
3. Installer must be a trained, experienced, flame 
safeguard control technician.
4. After installation is complete, check out product 
operation as provided in these instructions.
Disconnect power supply before beginning installation to 
prevent electrical shock and equipment damage. All wiring 
must comply with applicable electrical codes, ordinances 
and regulations. Use NEC Class 1 wiring.
IMPORTANT
Ultraviolet radiation sensing tubes have a life 
expectancy of 40,000 hours of continuous use within 
the flame detector's specified ambient temperature 
and voltage ratings. Wearout of an ultraviolet 
radiation sensing tube results in failure of the UV 
sensor to properly discriminate between flame 
conditions.
The C7027A, C7035A and C7044A Flame Detectors 
should only be used on burners that cycle on/off 
periodically or, in the absence of cycling, are 
periodically checked for proper operation.
Recommended industry standards for the frequency 
of sensor checks, either through cycling (employing 
safe-start check methods) or periodic maintenance, 
vary between once every ten seconds and once 
every week, depending on the standard used and 
the application needs.
Consult the equipment manufacturer or the 
governing standard for recommendations about 
frequency of checks.
Controls incorporating safe-start checks, and 
sensors and controls employing constant check 
means are available from Honeywell.  See your 
Honeywell representative for specific information.
4 FOOT (1.2 METER)
LEADWIRES (2)
M17783
3-1/4 (82)
3-3/4 (95)
1
(25)
C7927A1016
3-11/16
(94)
1 (25)
6-1/2 FT. (1.98M)
M17784
C7927A1008