Instruction Manual: COSTAR® 12SIR, 12V System CO Alarm 
QGI P/N 099-0066-01 REV 10/26/01 
Page 1 of 7 
 
 
 
COSTAR MODEL 12SIR 
Carbon Monoxide Gas Alarm 
12V System 
INSTALLATION and OPERATING 
INSTRUCTIONS 
 
UL2075 LISTED 
CARBON MONOXIDE GAS ALARM
 
 
Dear New COSTAR
®
 12SIR Owner, 
Congratulations as you have taken steps to help insure the health and life safety of you and your family.  We are proud to 
offer you our unique, patented CO Sensor technology that detects CO in a manner similar to the human body's response.  The 
COSTAR
®
 12SIR is an ideal and low-cost way of warning you of both the acute and chronic effects of CO poisoning. 
Please read this owner's manual carefully so you will have a better understanding of the effects of CO poisoning and the 
COSTAR
®
 12SIR Alarm, as we work together pursuing a safer, healthier indoor air quality for us all. 
 
To your good health and safety, 
 
Mark Goldstein, Ph.D. 
President  
Quantum Group Inc.
  
 
1.0 GENERAL 
DESCRIPTION 
This CO alarm is suited for residences, motels, hotels, and commercial or industrial system applications.  The 12SIR is designed for 4-
6 wire connection to 12VDC alarm system control panels. 
Reference:  UL Listed Household Fire and/or Burglary Panel with auxiliary signaling zones.  Connect to signaling zones which can be 
designated for CO alarm use only. 
 
2.0 PRODUCT 
DATA 
2.1 Sensitivity 
Setting: 
 
Unit will alarm at 150 ppm CO within 50 minutes. 
2.2 Power: 
 
12VDC nominal  
2.3 Current 
Draw: 
 
Standby 20 microAmp.  Alarm 60 mA.  Trouble 30 mA. 
2.4 Field 
Wiring: 
 14-22 
AWG 
2.5 Relay 
Contacts: 
 
Dry form 'C' (100 microAmp – 0.1A, 12VDC) non-latching 
2.6 Operating 
Temperature: 
 
4.4° C – 37.8° C (40° F - 100° F) 
2.7 Operating 
Humidity: 
 15-95% 
RH 
2.8 
Horn (Sounder) Loudness: 
 
85 db @ 10 ft (3.3 meters) 
 
3.0 APPROVALS 
 
 
Listed by Underwriters Laboratories Inc. to the Category Gas and Vapor Detectors and Sensors (FTAM).