Lennox Hearth MPD-4540CNM-B Manuale Utente

Pagina di 42
17
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
LENNOX HEARTH PRODUCTS  •  MERIT
®
 PLUS DIRECT VENT GAS FIREPLACES (MPD33/35/40/45)  •  INSTALLATION INSTRUCTIONS
Figure 31: Rear Vent - ONE 90-DEGREE ELBOW
Figure 30: Top Vent - STRAIGHT
Figure 32: Top Vent - TWO 90-DEGREE ELBOWS
VERTICAL VENT FIGURES/TABLES 
Note: It is very important that the horizontal/
inclined run be maintained in a straight (no dips) 
and recommended to be in a slightly elevated 
plane, in a direction away from the fireplace of 
1/4" rise per foot (20 mm per meter) which is 
ideal, though rise per foot run ratios that are 
smaller are acceptable all the way down to at 
or near level.
Note: SV4.5VF (Secure Vent), SF4.5VF (Secure 
Flex) firestop/spacer must be used anytime vent 
pipe passes through a combustible floor or ceil-
ing. SV4.5HF (Secure Vent), SF4.5HF (Secure 
Flex)firestop/spacer must be used anytime vent 
pipe passes through a combustible wall.
Note:  Two 45 degree elbows may be used in 
place of one 90 degree elbow. The same rise 
to run ratios, as shown in the venting figures 
for 90 elbows, must be followed if 45 degree 
elbows are used.  
Note:    An  elbow  is  acceptable  as  1  foot  of 
vertical rise, except where an elbow is the 
only vertical component in the system.  (See 
Figure 39 on page 21 ).
Note:  Secure  Vent  (rigid vent pipe)  is shown 
in the figures; Secure Flex (flexible vent pipe) 
may also be used.
A Vent Restrictor, as shown in Figure 
18 on Page 13, must be used in this 
application.
This table shows a 1 (V) to 2 (H) ratio.  
For every 1 foot of (V) vertical, you are 
allowed 2 feet of (H) horizontal run, up 
to a maximum horizontal run of 8 feet. 
Example: If 8 feet of (H) horizontal vent 
run is needed, then 4 feet minimum (V) 
vertical vent will be required.
TABLE  A
H Maximum
V Minimum
feet
feet
2
(0.610)
1
(0.305)
4
(1.219)
2
(0.610)
6
(1.829)
3
(0.914)
8
(2.438)
4
(1.219)
V + H = 40 feet (12.2 meters) Max.
H = 8 feet (2.4 meters) Max.
Ratio V to H ratio is 1:2
(meters)
(meters)
Example:  If 20 feet of (H) horizon-
tal vent run is needed, then 4 feet 
minimum  of  (V)  vertical  vent  will 
be required.
This table shows a 1 (V) to 5 (H) ratio.  
For every 1 foot of (V) vertical, you 
are allowed 5 feet of (H) horizontal 
run,  up  to  a  maximum  horizontal 
run of 20 feet.
An elbow is acceptable as 1 foot of 
vertical rise except where an elbow 
is the only vertical component in the 
system.  See Figure 39.
TABLE  B
H Maximum
V Minimum
feet
(meters)
feet
5
(1.524)
Elbow Only
5
(1.524)
1
(0.305)
10
(3.048)
2
(0.610)
15
(4.572)
3
(0.914)
20
(6.096)
4
(1.219)
V + V
1
+ H = 40 feet (12.2 m) Max.
H = 20 feet (6.096 meters) Max.
(meters)
        
WARNING
Separate  sections  of  concentric  flexible  vent  pipe  may  NOT  be  joined 
together under any circumstances.
Max. 40 ft
(12.2 m)
*When using 
  Secure Flex, use
  Ceiling Firestop/
  Spacer SF4.5VF
Ceiling
Firestop/
Spacer
SV4.5VF*
V
H
Ceiling
Firestop/Spacer
SV4.5VF*
*When using Secure Flex, use
  Ceiling Firestop/Spacer 
SF4.5VF
H
V
V1
Ceiling
Firestop/Spacer
SV4.5VF*
Wall
Firestop/Spacer
SV4.5HF**
  *When using Secure Flex, use
    Ceiling Firestop/Spacer SF4.5VF.
**When using Secure Flex, use
    Wall Firestop/Spacer SF4.5HF