 PLUS DIRECT VENT GAS FIREPLACES (MPD33/35/40/45)  •  INSTALLATION INSTRUCTIONS
B. Brush all joints and connections with the gas 
leak test solution to check for leaks. If bubbles 
are formed, or gas odor is detected, turn the 
gas  control  knob  (off/pilot/on)  to  the  “OFF” 
position.  Either tighten or refasten the leaking 
connection, then retest as described above.
C. When the gas lines are tested and leak free, 
be sure to rinse off the leak testing solution.
Step 8. VERIFYING APPLIANCE 
OPERATION
With  gas  line  installed,  run  initial  system 
checkout before closing up the front of the 
unit.    Follow  the  pilot  lighting  instructions 
provided in the Care and Operation Instruc-
tions.  For  piezo  igniter  location  on  millivolt 
appliances, see Figure 47 on Page 25.
Note: lighting Instructions are also found on 
the  literature  tag  tied  to  the  gas  piping  next 
to the gas valve. To access the tag, open the 
lower control compartment door (Figure 52) 
by pushing in simultaneously the left and right 
top corners of the door. (The door is hinged at 
the bottom).  Remove the bottom compartment 
door by sliding the hinge pin, located at the 
door’s left side, to the right until it disengages 
from the left corner post hole.
When first lighting the appliance, it will take a 
few minutes for the line to purge itself of air. 
Once purging is complete, the pilot and burner 
will light and operate as indicated in the instruc-
tion manual.  
Turn on gas supply and test for gas leaks, us-
ing a gas leak test solution (also referred to as 
bubble leak solution).  
Note:  using a soapy water solution is an effec-
tive leak test solution but it is not recommended, 
because  the  soap  residue  that  is  left  on  the 
pipes/fittings can result in corrosion over time. 
A. Light  the  appliance  (refer  to  the  lighting 
instructions label in the control compartment 
or  in  the  Care  and  Operation  Instructions 
manual).
MILLIVOLT
Thermocouple
Hood Igniter Rod
3/8" Min
(9 mm)
Thermopile
Pilot
Nozzels
Subsequent lighting of the appliance will not 
require such purging. Inspect the pilot flame 
(remove logs, if necessary, handling carefully).
Millivolt Appliance Checkout
The  pilot  flame  should  be  steady,  not  lifting 
or floating. Flame should be blue in color with 
traces of orange at the outer edge.
The  top  3/8"  (10  mm)  at  the  pilot  generator 
(thermopile) and the top 1/8" minimum (tip) 
of the quick drop out thermocouple should be 
engulfed in the pilot flame. 
The flame should project 1" (25 mm) beyond 
the hood at all three ports  (see Figure 53).   
Replace logs if removed for pilot inspection.
To light the burner; turn “ON” the remote wall 
switch and rotate the gas valve control knob 
counterclockwise to the “ON” position (“ON” 
will be at the top side of the valve).
Electronic Appliance Checkout
To light the burner, turn ‘ON’ the unit-mounted 
ON/OFF  switch  or  the  optional  remote  wall 
switch.  Ensure the igniter lights the pilot.  The 
pilot flame should engulf the flame rod as shown 
in Figure 54.
Figure 53
Figure 52
Figure 51: Gas Connection
Gas
Stub
1/2" x 3/8" Flare
Shut-Off Valve
3/8" Flex Tubing
3/8" NPT x 3/8"
Flare Fitting
3/8" Nipple
3/8" Union
3/8" Close Nipple
3/8" Shut-Off Valve
1/2" x 3/8"
Reducer
Gas
Valve
Optional Gas Flex Line Connector
ELECTRONIC
Proper Flame
Adjustment
Pilot
Nozzle
3/8 To 1/2 Inch
(9 mm to 13 mm)
Ground
Electrode
Flame Rod
Hot Surface
Igniter
Figure 54
Millivolt Gas Valve Showing 
Piezo Ignitor Location 
Piezo
Ignitor
SIT Gas Valve