CHIIMNEY INSTALLATION 
1.  Extend the regular chimney sections until the top of the chimney is 4" 
below the total flue height desired. Do not snap the last section of inlet 
air duct or largest diameter pipe in place until Step 3 is completed.
2.  Remove the shingles from around the chimney so that the flashing 
may be installed. Install the upper part of the flashing under the 
shingles.
3.  Set the flashing on the roof. Scribe a line around the flashing. Cut 
1
/
4
" below the scribed line. This should increase the diameter of the 
flashing outlet enough to allow the flashing to be placed over the 
chimney. See Figure 25.
4.  Snap the last section of inlet air duct in place. Slide flashing over the 
chimney. Check for minimum clearances. Adjust chimney if neces-
sary to make minimum clearances. 
5.  Nail the flashing securely in place with eight (8) nails.
6.  Seal crack between top of flashing and chimney with mastic. Leave 
some extra mastic at this area to be used in step 8. 
Be  careful  to  avoid  electrical  shock 
hazard  when  contacting  wires  to  the 
metal chimney components.
CAUTION 
Use  pliers  and  wear  gloves  when 
handling the storm color The edge of 
the storm color is sharp. If you are not 
careful, you could cut your hands.
CAUTION 
CHIMNEY CAP INSTALLATION 
(CONTINUED)
Cut Off 
1
/
4
below Scribed 
Line
Figure 25 - Cutting Off Top of the 
Flashing 
Flashing 
Figure 26 - Installing Storm Collar 
and Chimney Cap 
Model SC 
Chimney Cap 
Apply Mastic 
Here
 
Storm Collar
 
  Flashing 
9.  Place chimney cap into matching parts of the last chimney section. Push chimney cap down until the brackets on the 
bottom of the chimney cap sits on the chimney pipe. Punch or drill 
1
/
8
" diameter holes in the inlet air duct (chimney pipe) 
where specified on the brackets. Fasten chimney pipe down with the No. 8 screws provided. Note: Do not penetrate 
the inner stainless steel pipe while installing the screws.
10. Check all the parts of the fireplace, chimney and chimney termination cap. Make sure none have been damaged or bent 
during installation. Check to see that all parts have been properly installed. 
Note: The metal used for chimney cap has a rust-protective coating but the cut edges of the parts are not 
protected. Detergent-wash and paint exposed parts of chimney cap with galvanized primer paint. 
This will prevent rusting and rust staining of nearby structures. 
7.  Place the storm collar around the chimney and put collar 
together like a belt in belt loops. With the loops facing 
up, slide the end of collar under the two loops on the 
other end. Overlap the ends of the collar until it is tight 
against the chimney. Bend the free end of the collar back 
over the loops to hold the storm collar securely together. 
Trim off the excess ends of the storm collar. 
8.  Slide storm collar down snugly against the flashing until 
the excess mastic left in step six is forced up into crack 
between the storm collar and chimney. This will make the 
joint between the flashing and the chimney watertight. 
See Figure 26.