The clearances listed below are minimum distances unless otherwise stated:
A major cause of chimney related fi res is failure to maintain required clearances (air space) to combustible materials. It is of the greatest 
importance that this fi replace and vent system be installed only in accordance with these instructions.
Clearance to Combustibles from:
Back 0" 
(0mm) 
Side 0" 
(0mm) 
Floor 0"* 
(0mm)
* Note: A hearth is required, unless the unit is raised
  4" (102mm), see "Hearth Requirements" section for details.
Minimum Clearance from Top of Louver Opening:
Mantel Height min. 12"  (305mm) (at 1" mantel depth) 
Ceiling 39" (990mm) 
Side Wall to Unit:
  
8" 
(203mm)
Horizontal Vent Clearances to Combustibles:
Top 
2-1/2" (64mm)
Side 
1-1/2" (38mm)
Bottom 
1-1/2" (38mm)
Vertical  Vent  Clearances to Combustibles:
All Sides 1-1/4" 
(32mm) 
Alcove Clearances:
Max. Depth 36" 
(914mm)
Min. Width 56" 
(1422mm)
Min. Height 72" 
(1829mm)
INSTALLATION
Caution Requirements
The top,  back and sides of the fi replace are defi ned by 
standoffs. The metal ends of the standoff may NOT be 
recessed into combustible construction.
WARNING
Fire hazard is an extreme risk 
if these clearances (air space) to combustible materials 
are not adhered to. It is of greatest importance that this 
fi replace and vent system be installed only in
accordance with these instructions.