GAS LINE REQUIREMENTS
The gas line must be installed in accordance with all local codes, if any; if not, follow
ANSI 223.1 and the requirements listed below.  Ensure that a 1 1/4" allowance from
base of unit is made for hard pipe installation, see page 16, Minimum Framing Dimen-
sions.
The fireplace and gas control valve must be disconnected from the gas supply piping
during any pressure testing of that system at test pressures in excess of 1/2 psig.  For
pressures under 1/2 psig, isolate the gas supply piping by closing the manual shutoff
valve.
The appliance must be isolated from the gas supply piping system by closing its equip-
ment shutoff valve during any pressure testing of the gas supply piping system at test
pressures equal to or less than 1/2 psi (3.5 kPa).
Leak  test  all  gas  line  joints  and  the  gas  control  valve  prior  to  and  after  starting  the
fireplace.
Fuel
This  unit  is  manufactured    for  use  with    natural  gas.   To  convert  to  LP  gas,  Part
#842-4470,  LP Conversion Kit,  is required and available through your dealer
Gas Line Connection
A  manual shutoff valve is installed in the unit. To access the shutoff valve, open the
control  panel  access  door  and  locate  the  red  swing  handle    to  the    right  of  the
control panel beneath the firebox.
Gas Inlet Pressure

All  other  gas  appliances  in  the  household  must  be  turned  “ON”  to
check Inlet Pressure, and;

Inlet pressure can only be checked with fireplace burner “ON”.
If the pressure is not sufficient, ensure: 1) the piping used is large enough, 2)
the supply regulator is adequately adjusted, and 3) that  the total gas load for
the residence does not exceed the amount supplied.
The supply regulator (the regulator that attaches directly to the residence inlet
or  to  the  propane  tank)  should  supply  gas  at  the  suggested  input  pressure
listed above.  Contact the local gas supplier if the regulator is at an improper
pressure.
GAS 
LINE
Input Pressure
Standard
Minimum
Maximum
Natural Gas
7" W.C.
4.5"W.C.
7"W.C.
Propane
11" W.C.
11"W.C.
14"W.C.