In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code
2
 
In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code
+
 
A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single 
family dwellings and serves both dwellings.
**  Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the 
floor.
For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, one of the following shall be 
indicated:
a) A minimum clearance value determined by testing in accordance with section 4.7.3, 6.5.5, 8.5.5; or;
b) A reference to the following footnote:
"Clearance in accordance with local installation codes and the requirements of the gas supplier."
H
Clearance to each 
side of center line 
extended above 
meter/regulator 
assembly
3' (91 cm) within a height 15' (4.5 m) above 
the meter/regulator assembly
*
I
Clearance to
 service regulator 
vent outlet
3' (91 cm)
*
J
Clearance to non-
mechanical air 
supply inletto 
building or the 
combustion air inlet 
to any other 
appliance
12" (30 cm)
9" (23 cm)
K
Clearance to 
mechanical air sup-
ply inlet
6' (1.83 m)
3' (91 cm) above if within 10' (3 m) 
horizontally
L
Clearance above 
paved sidewalks or 
paved driveway 
located on private 
property
7' (2.13 m)
+
7’ (2.13 m)
+
M
Clearance under 
veranda, porch, 
deck, or balcony
12' (30 cm)**
12" (30 cm)**