Desa FPVF33PRA Manuale Utente

Pagina di 40
www.desatech.com
113109-01C
 
Example:
 
Gas water heater    ______________ Btu/Hr
 
Vent-free fireplace + _____________ Btu/Hr
 
Total  
= _____________ Btu/Hr
4.  Compare the maximum Btu/Hr the space can 
support with the actual amount of Btu/Hr used.
 
 _________Btu/Hr (maximum the space can support) 
 
 _________Btu/Hr (actual amount of Btu/Hr used)
 
Example:
  51,200 Btu/Hr (maximum the space 
can support) 
 
 
73,000  Btu/Hr  (actual  amount  of 
Btu/Hr used)
The space in the above example is a confined space 
because the actual Btu/Hr used is more than the maxi-
mum Btu/Hr the space can support. You must provide 
additional fresh air. Your options are as follows:
A.  Rework worksheet, adding the space of an adjoin-
ing room. If the extra space provides an unconfined 
space, remove door to adjoining room or add 
ventilation grills between rooms. See Ventilation 
Air From Inside Building.
B.  Vent room directly to the outdoors. See Ventila-
tion Air From Outdoors.
C.  Install a lower Btu/Hr fireplace, if lower Btu/Hr 
size makes room unconfined. 
If the actual Btu/Hr used is less than the maximum 
Btu/Hr the space can support, the space is an uncon-
fined space. You will need no additional fresh air 
ventilation.
 WARNING: If the area in which 
the  fireplace  may  be  operated 
is  smaller  than  that  defined  as 
an  unconfined  space  or  if  the 
building  is  of  unusually  tight 
construction, provide adequate 
combustion and ventilation air by 
one of the methods described in 
the National Fuel Gas Code, ANSI 
Z223.1/NFPA  54  Section  5.3  or 
applicable local codes. 
vENTILATION AIR
Ventilation Air From Inside Building 
This fresh air would come from an adjoining un-
confined space. When ventilating to an adjoining 
unconfined space, you must provide two perma-
nent openings: one within 12" of the ceiling and 
one within 12" of the floor on the wall connecting 
  40,000
  33,000
  73,000
AIR FOR COMbUSTION 
AND VENTILATION
Continued
Figure 3 - Ventilation Air from Inside 
Building
Or
Remove
Door into
Adjoining
Room,
Option
3
Ventilation Grills 
Into Adjoining Room,
Option 2
Ventilation
Grills 
Into Adjoining 
Room,
Option 1
12"
12"
the two spaces (see options 1 and 2, Figure 3). You 
can also remove door into adjoining room (see 
option 3, Figure 3). Follow the National Fuel Gas 
Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for 
Combustion and Ventilation for required size of 
ventilation grills or ducts.
Figure 4 - Ventilation Air from Outdoors
Outlet
Air
Ventilated
Attic 
Outlet
Air
Inlet
Air
Inlet Air
Ventilated 
Crawl Space
To 
Crawl
Space
To Attic
ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or 
ducts. You must provide two permanent openings: 
one within 12" of the ceiling and one within 12" 
of the floor. Connect these items directly to the 
outdoors or spaces open to the outdoors. These 
spaces include attics and crawl spaces. Follow the 
National Fuel Gas Code, ANSI Z223.1/NFPA 54, 
Section 5.3, Air for Combustion and Ventilation for 
required size of ventilation grills or ducts. 
IMPORTANT:
 Do not provide openings for inlet 
or outlet air into attic if attic has a thermostat-
controlled power vent. Heated air entering the attic 
will activate the power vent.