LOW AMBIENT CONDENSER FAN CONTROL
For unit operation below 25°F (-3.9°C) a low ambient
kit is required. The kit consists of a discharge pressure
transducer(s) and reversing contactors.
With the low ambient kit installed and the unit pro-
grammed for low ambient operation, the condenser fans
will operate as shown in Tables 41 and 42.
TABLE 41 
LOW AMBIENT CONDENSER FAN CONTROL – AMBIENT TEMPERATURE AND DISCHARGE
PRESSURE CONTROL
Again, notice that condenser fan operation can be pro-
grammed for either “temperature and discharge pres-
sure control,” or “discharge pressure control only” as
described under Condenser Fan Control.
The fan control on-pressure (ctrl_press) and the fan def-
erential off-pressure (diff_press) are programmable un-
der the PROGRAM key.
TABLE 42 – LOW AMBIENT CONDENSER FAN CONTROL –  DISCHARGE PRESSURE CONTROL
2
FAN STAGE
ON
OFF
1
OAT >25° F (-3.9°C)
OAT < 20° F (-6.7°C)
1 FAN REV
OR
AND
DP > ctrl_press
DP < ctrl_press - diff_press
2
OAT >45°F  (7.2°C)
OAT < 40°F (-4.40°C)
1 FAN FWD
OR
AND
DP > ctrl_press  + 20 PSIG  (1.38 Bars)
DP < ctrl_press  - diff_press + 20 PSIG  (1.38 Bars)
3
OAT > 65°F (18.3°C)
OAT < 60°F (15.6°C)
2 FANS FWD
OR
AND
DP > ctrl_press + 40 PSIG (2.76 Bars)
DP < ctrl_press - diff_press + 40 PSIG (2.76 Bars)
FAN STAGE
ON
OFF
1
1 FAN REV
DP > ctrl_press
DP < ctrl_press - diff_press
2
1 FAN FWD
DP > ctrl_press  + 20 PSIG  (1.38 Bars)
 DP < ctrl_press  - diff_press + 20 PSIG  (1.38 Bars)
3
2 FANS FWD
DP > ctrl_press + 40 PSIG (2.76 Bars)
DP < ctrl_press - diff_press + 40 PSIG (2.76 Bars)