Mitsubishi P336 Manuale Utente

Pagina di 334
I  Read Before Servicing ]
- 6 -
HWE09120
GB
4.  Thickness and refrigerant type indicated on the piping materials
Ask the pipe manufacturer for the symbols indicated on the piping material for new refrigerant.
5.  Flare processing (O-material (Annealed) and OL-material only)
The flare processing dimensions for the pipes that are used in the R410A system are larger than those in the R22 system.
If a clutch-type flare tool is used to flare the pipes in the system using R410A, the length of the pipes must be between 1.0 
and 1.5 mm. For margin adjustment, a copper pipe gauge is necessary.
6. Flare 
nut
The flare nut type has been changed to increase the strength. The size of some of the flare nuts have also been changed.
The figures in the radial thickness column are based on the Japanese standards and provided only as a reference. Use pipes 
that meet the local standards.
Flare processing dimensions (mm[in])
Pipe size (mm[in])
A dimension (mm)
R410A
R22, R407C
ø6.35
[1/4"]
9.1
9.0
ø9.52
[3/8"]
13.2
13.0
ø12.7
[1/2"]
16.6
16.2
ø15.88
[5/8"]
19.7
19.4
ø19.05
[3/4"]
24.0
23.3
Flare nut dimensions (mm[in])
Pipe size (mm[in])
B dimension (mm)
R410A
R22, R407C
ø6.35
[1/4"]
17.0
17.0
ø9.52
[3/8"]
22.0
22.0
ø12.7
[1/2"]
26.0
24.0
ø15.88
[5/8"]
29.0
27.0
ø19.05
[3/4"]
36.0
36.0
Dimension A
Dimension B