Mitsubishi P336 Manuale Utente

Pagina di 334
VIII  Test Run Mode ]
- 146 -
HWE09120
GB
Operation
Outdoor unit model
PUHY-P288TSJMU-A
PUHY-P144TJMU-A
PUHY-P144TJMU-A
Operating 
conditions
Ambient 
tempera-
ture
Indoor
DB/WB
21.1°C/ - [70°F/ - ]
Outdoor
8.3°C/6.1°C [47°F/43°F]
Indoor 
unit
No. of connected 
units
Unit
4
No. of units in opera-
tion
4
Model
-
36/36/36/36
Piping
Main pipe
m [ft]
5 [16-3/8]
Branch pipe
10 [32-3/4]
Total pipe length
45 [147-5/8]
Fan speed
-
Hi
Amount of refrigerant
kg
[lbs-oz]
27 [59]
Outdoor 
unit
Electric current
A
75.1
Voltage
V
230
Compressor frequency
Hz
102
102
LEV open-
ing
Indoor unit
Pulse
332/332/332/332
332/332/332/332
SC (LEV1) 
0
0
LEV2
2100
2100
Pressure
High pressure (after O/S)/low 
pressure (before accumulator)
MPa
[psi]
2.74/0.61 [397/88]
2.74/0.61 [397/88]
Temp. of 
each sec-
tion
Outdoor 
unit
Discharge (TH4)
°C [°F]
89 [192]
89 [192]
Heat exchanger out-
let (TH3)
-3 [27]
-3 [27]
Accumulator inlet
-3 [27]
-3 [27]
Accumulator outlet
-3 [27]
-3 [27]
Compressor inlet
-3 [27]
-3 [27]
Compressor shell 
bottom
40 [104]
40 [104]
Indoor 
unit
LEV inlet
37 [99]
37 [99]
Heat exchanger  
inlet
80 [176]
80 [176]