Lg Electronics General Wall Mounted-Inverter Type Manuale Utente

Pagina di 67
16 Room Air Conditioner
Part 2   Functions & Controls
5.1  Five Seconds Stand-by (fan)
• The indoor unit fan rotates after 5 seconds when unit is turned on.
5.2  Two Minutes Stand-by (comp.) 
• Compressor starts two minutes later, after it is turned off
5.3  Hot start
• When unit starts in the heating mode to prevent cold wind blowing, the indoor fan does not rotate until the temp. of
heat exchanger reaches 30°C(86°F)(model by model)
5.4  Freeze prevention (Protection of the evaporator pipe from frosting)
• If the indoor pipe temperaure is below 0°C(32°F) in 7 min. after the compressor operates without pause while in cool-
ing cycle operation mode, 
➔ compressor, outdoor fan are turned off.
• When indoor pipe temp. is 7°C(44.6°F) or higher after 2 min pause of compressor 
➔ compressor, outdoor fan is turned
on according to the condition of the room temperature.
5. Protection Functions & Controls
Comp. free
Comp. Step 4
Comp. Step 2
Comp. off
T1
3˚C(37.4˚F)
6˚C(42.8˚F)
7˚C(44.6˚F)
Indoor pipe
temp.
T1: 0 ~ 2°C(32~35.6°F)
NOTE: Some Models are different by T1.