Lg Electronics LA120CPO Manuale Utente

Pagina di 76
62 Room Air Conditioner
Troubleshooting Guide 
Cycle Parts
Trouble analysis 
1. Check temperature difference between intake and discharge air and operating current. 
Temp. Difference 
Temp. difference   :   approx. 0˚F(0°C)
Current                  :   less than 80% of 
rated current  
Temp. difference   :   approx. 14°F(8°C)
Current                  :   less than 80% of 
rated current  
Temp. difference   :   less than 14°F(8°C)
Current                  :   over the reated
current 
Temp. difference   :   over 14°F(8°C)
Operating Current 
• All amount of refrigerant leaked
out. Check refrigeration cycle.
• Refrigerant leakege
Clog of refrigeration cycle
Defective compressor 
• Excessive amount of refrigerant
• Normal 
Temperature difference between intake and discharge air depends on room air humidity. When the room air
humidity is relativery higher, temperature difference is smaller. When the room air humidity is relatively lower
temperature difference is larger. 
2. Check temperature and pressure of refrigeration cycle. 
1. The suction pressure is usually 4.5~6.0 kg/cm
2
G(Cooling) at normal condition. 
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with
putty. 
NOTICE
NOTICE
Suction pressure
Temperature
(Compared with
(Compared with
Cause of Trouble
Description
the normal value)
the normal valve)
Defective compressor
Current is low.
Defective 4-way reverse valve
Excessive amount of
High pressure does not quickly
Normal
refrigerant
rise at the beginning of 
operation.
Insufficient amount of 
Current is low.
Lower Higher
refrigerant 
(Leakage)
Clogging
Current is low.
High 
Higher